Input/Output
Terminals
Power Supply Specifications
Serial communication input/output
D+, D-, AC
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external power
supply.
24 V external power supply
PS, AC
Use the UL Listed class 2 power supply.
◆
Drive Motor Overload and Overheat Protection
The drive motor overload and overheat protection function complies with the National Electric Code (NEC) and the
Canadian Electric Code, Part I (CEC).
Set the Motor Rated Current and
L1-01 through L1-04 [Motor Overload Protection Select]
correctly to enable motor
overload and overheat protection.
Refer to the control method and set the motor rated current with
E2-01 [Motor Rated Current (FLA)]
,
E5-03 [PM
Motor Rated Current (FLA)]
, or
E9-06 [Motor Rated Current (FLA)]
.
■
E2-01: Motor Rated Current (FLA)
No.
(Hex.)
Name
Description
Default
(Range)
E2-01
(030E)
Motor Rated Current (FLA)
Sets the motor rated current in amps.
Determined by o2-04, C6-01
(10% to 200% of the drive
rated current)
Note:
•
If
E2-01 < E2-03 [Motor No-Load Current]
, the drive will detect
oPE02 [Parameter Range Setting Error]
.
•
When the drive model changes, the display units for this parameter also change.
–
0.01 A: models 2004 - 2042, 4002 - 4023
–
0.1 A: models 2056 - 2415, 4031 - 4H12, T103 - T720
The value set for
E2-01
becomes the reference value for motor protection, the torque limit, and torque control. Enter
the motor rated current written on the motor nameplate. Auto-Tuning the drive will automatically set
E2-01
to the
value input for
“
Motor Rated Current
”
.
■
E5-03: PM Motor Rated Current (FLA)
No.
(Hex.)
Name
Description
Default
(Range)
E5-03
(032B)
Motor Rated Current (FLA)
Sets the PM motor rated current (FLA).
Determined by E5-01
(10% to 200% of the drive
rated current)
Note:
The display units are different for different models:
•
0.01 A: models 2004 - 2042, 4002 - 4023
•
0.1 A: models 2056 - 2415, 4031 - 4H12, T103 - T720
The drive automatically sets
E5-03
to the value input for
“
PM Motor Rated Current
”
after you do these types of Auto-
Tuning:
•
Manual Entry w/ Motor Data Sheet
•
PM Stationary Auto-Tuning
•
Stationary (R Only)
•
Rotational (Ld, Lq, R, back-EMF)
■
E9-06: Motor Rated Current (FLA)
No.
(Hex.)
Name
Description
Default
(Range)
E9-06
(11E9)
Motor Rated Current (FLA)
Sets the motor rated current in amps.
Determined by E9-01 and
o2-04
(10% to 200% of the drive
rated current)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV