YASKAWA
TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
485
2.
Push
[Menu].
3.
Push
or
to select [Diagnostic Tools], then push
.
4.
Push
or
to select [Drive Information], then push
.
The keypad will show the drive information.
A - Drive Series
B - Maximum Applicable Motor Output (HD/ND)
C - Rated Output Current (HD/ND)
D - Drive software version
E - Serial number
◆
Write Automatically Backed-up Parameters to the Drive
You can automatically back up parameters to the keypad connected to the drive and write those parameters to a drive
from the same drive series as specified by the settings of
o3-06 [Auto Parameter Backup Selection]
and
o3-07
[Period setting of auto backup]
.
Note:
•
Set
o3-06 = 1 [Auto Parameter Backup Selection = Enabled]
in each drive to which you will write the parameters.
•
This operation is not available when the parameters in the keypad and the parameters on the other drives are set to the same values.
1.
Connect the keypad to the drive.
2.
Push
or
to select [Yes], then push
.