YASKAWA
TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
159
No.
(Hex.)
Name
Description
Default
(Range)
b3-14
(019E)
Bi-directional Speed Search
Sets the direction of Speed Search to the direction of the frequency reference or in the motor rotation
direction as detected by the drive.
0 : Disable
1 : Enabled
Note:
•
The initial value of
b3-14
is different for different
A1-02 [Control Method Selection]
settings
when you set these parameters:
–
A1-02 = 0, 2, 8 [V/f, OLV, EZOLV]
–
E9-01 = 0 [Motor Type Selection = Induction (IM)]
–
b3-24 = 1 [Speed Search Method Selection = Speed Estimation]
.
•
The initial value of
b3-14
is different for different
A1-02 [Control Method Selection]
settings
when you set these parameters:
–
A1-02 = 1, 4, 8 [CL-V/f, AOLV, EZOLV]
–
E9-01 = 1, 2 [Permanent Magnet (PM), Synchronous Reluctance (SynRM)]
•
The initial value of
b3-14
is 0 when you set these parameters:
–
A1-02 = 0, 2, 8
–
E9-01 = 0
–
b3-24 = 2 [Current Detection 2]
•
When you set
A1-02
,
b3-24
, and
E9-01
, set
b3-14
.
Determined by A1-02, b3-
24, and E9-01
(0, 1)
b3-17
(01F0)
Expert
Speed Est Retry Current
Level
Sets the current level for the search retry function in Speed Estimation Speed Search as a percentage
where drive rated current is a setting value of 100%.
150%
(0 - 200%)
b3-18
(01F1)
Expert
Speed Est Retry Detection
Time
Sets the length of time that the drive will wait to retry Speed Estimation Speed Search when too
much current flow stopped the Speed Search.
0.10 s
(0.00 - 1.00 s)
b3-19
(01F2)
Speed Search Restart
Attempts
Sets the number of times to restart Speed Search if Speed Search does not complete.
3 times
(0 - 10 times)
b3-24
(01C0)
Speed Search Method
Selection
Sets the Speed Search method when you start the motor or when you restore power after a
momentary power loss.
Note:
•
When
A1-02 = 8 [Control Method Selection = EZOLV]
, the default setting changes when the
setting for
E9-01 [Motor Type Selection]
and the drive model change.
–
E9-01 = 0 [Induction (IM)]
–
2004 to 2313, 4002 to 4302, T103 to T302: 1
–
2360, 2415, 4371 to 4720, T371 to T720: 2
–
E9-01 = 1, 2 [Permanent Magnet (PM), Synchronous Reluctance (SynRM)]: 1
•
When you set
A1-02 = 8
and
E9-01 = 1 or 2
, also set
b3-24 = 1
. If
b3-24 = 2
, the drive will
detect
oPE08 [Parameter Selection Error]
.
•
When you set
b3-24
, it will trigger the drive to initialize
b3-14 [Bi-directional Speed Search]
.
After you set
b3-24
, set
b3-14
.
1 : Speed Estimation
2 : Current Detection 2
2
(1, 2)
b3-25
(01C8)
Expert
Speed Search Wait Time
Sets the length of time the drive will wait to start the Speed Search Retry function.
0.5 s
(0.0 - 30.0 s)
b3-26
(01C7)
Expert
Direction Determination
Level
Sets the level to find the motor rotation direction. Increase the value if the drive cannot find the
direction.
1000
(40 to 60000)
b3-27
(01C9)
Expert
Speed Search RUN/BB
Priority
Sets the conditions necessary to start Speed Search.
0 : SS Only if RUN Applied Before BB
1 : SS Regardless of RUN/BB Sequence
0
(0, 1)
b3-29
(077C)
Expert
Speed Search Back-EMF
Threshold
Sets the induced voltage for motors that use Speed Search. The drive will start Speed Search when
the motor induced voltage level is the same as the setting value. Usually it is not necessary to change
this setting.
10%
(0 - 10%)
b3-31
(0BC0)
Expert
Spd Search Current
Reference Lvl
Sets the current level that decreases the output current during Current Detection Speed Search.
1.50
(1.50 - 3.50)
b3-32
(0BC1)
Expert
Spd Search Current
Complete Lvl
Sets the current level that completes Speed Search.
1.20
(0.00 - 1.49)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...