TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
No.
(Hex.)
Name
Description
MFAO Signal Level
U4-16
(07D8)
Motor oL1 Level
Shows the integrated value of
oL1 [Motor Overload]
as a percentage of
oL1
detection level.
Unit: 0.1%
10 V: 100%
U4-18
(07DA)
Reference Source
Shows the selected frequency reference source.
The keypad shows the frequency reference source as
“
XY-nn
”
as specified by these rules:
X:
External Reference 1/2 Selection [H1-xx = 2]
selection status
•
1:
b1-01 [Frequency Reference Selection 1]
•
2:
b1-15 [Frequency Reference Selection 2]
Y-nn: Frequency reference source
•
0-01: Keypad (
d1-01 [Reference 1]
)
•
1-00: Analog input (unassigned)
•
1-01: MFAI terminal A1
•
1-02: MFAI terminal A2
•
1-03: MFAI terminal A3
•
2-02 to 2-17: Multi-step speed reference (
d1-02 to d1-17 [Reference 2 to 16, Jog Reference]
)
•
3-01: MEMOBUS/Modbus communications
•
4-01: Communication option card
•
5-01: Pulse train input
•
7-01: DriveWorksEZ
•
9-01: Up/Down command
No signal output available
U4-19
(07DB)
Modbus FreqRef (dec)
Shows the frequency reference sent to the drive from the MEMOBUS/Modbus communications as a
decimal.
Unit: 0.01%
10 V: Maximum frequency
(0 V to +10 V)
U4-20
(07DC)
Option Freq Ref(dec)
Shows the frequency reference sent to the drive from the communication option as a decimal.
Unit: 0.01 %
10 V: Maximum frequency
(0 V to +10 V)
U4-21
(07DD)
Run Command Source
Shows the selected Run command source.
The keypad shows the Run command source as
“
XY-nn
”
as specified by these rules:
X:
External Reference 1/2 Selection [H1-xx = 2]
selection status
•
1:
b1-02 [Run Command Selection 1]
•
2:
b1-16 [Run Command Selection 2]
Y: Run command source
•
0: Keypad
•
1: Control circuit terminal
•
3: MEMOBUS/Modbus communications
•
4: Communication option card
•
7: DriveWorksEZ
nn: Run command limit status data
•
00: No limit status.
•
01: The Run command was left ON when the drive stopped in the Programming Mode.
•
02: The Run command was left ON when switching from LOCAL Mode to REMOTE Mode.
•
03: The Run command is in standby after the drive was energized until the soft charge bypass
contactor turns ON.
Note:
The drive will detect
Uv1 [DC Bus Undervoltage]
or
Uv [Undervoltage]
if the soft charge
bypass contactor does not turn ON after 10 s.
•
04: Restart after run stop is prohibited.
•
05: Fast stop has been executed using the MFDI terminal. Or, the motor has ramped to stop by
pressing the STOP key on the keypad.
•
06:
b1-17 = 0 [Run Command at Power Up = Disregard Existing RUN Command]
is set.
•
07: During baseblock while coast to stop with timer.
•
08: Frequency reference is below
E1-09 [Minimum Output Frequency]
during baseblock.
•
09: Waiting for the Enter command from PLC.
No signal output The keypad
shows the Run command
source as "XY-nn" as
specified by these rules:
available
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...