PAGE 8
Aquavar IPC Start-Up Genie
CentriPro
Select Yes to Autoset the rest of the settings.
For Simplex configuration, here are the
parameters that will get autoset:
Autoset Configuration
Constant
Pressure
Transducer Max Feedback
300 [unit]
Transducer Type
4-20mA
Feedback 1 Source
AI 53
PID Performance
Normal
Sleep Mode
Enabled
Sleep Frequency
30 Hz
Restart Difference
5 [unit]
No Water/Loss of Prime Fault
Enabled
No Water/Loss of Prime Restart Time
10 min.
Select Setpoint 1
Proceed with the down arrow on the next
two screens as you are verifying that your
Pressure Transducer is a 300 PSI, you are
wired in on Analog Input 53, that your
sleep frequency is 30 Hz, and your restart
difference is 5%, the No Water loss of prime
fault is enabled, and your restart time is 10
Minutes.
Cycle Power Off and prepare control wiring