PAGE 26
Aquavar IPC Start-Up Genie
CentriPro
1. Sending a 4-20 MA input signal to the drive using
analog input #53. You will wire your 4-20MA signal
into Terminal #53 and common on Terminal #55.
Dipswitch is defaulted for 4-20MA on analog input
#53
2. Sending a 0-10VDC input signal to the drive using
analog input #54. You will wire your 0-10VDC signal
into Terminal #54 and common on Terminal #55.
Dipswitch is defaulted to 0-10VDC on analog input
#54.
3. Running your pump and motor at one fixed speed
without sending a signal to the analog inputs. No
wiring is required other than the Start/Stop on
terminals #12 and #18.
When running your startup Genie for the first time,
please enter all of your motor information correctly.
• When you come to
the Operation Mode
selection, please
select Speed Control.
You can also get to this section from the main screen
by selecting:
• Quick Menu and
Selecting #4 Startup
Genie
SETTING UP THE INTELLIGENT PUMP CONTROLLER TO RUN IN SPEED CONTROL (IM295)
The Intelligent Pump Controller can be configured for speed control through an analog input. The controlling
source can be either an external control device such as a PLC, BMS, (Building Management System) or
potentiometer. The output from the external control device can be either a voltage or current output signal. Set
the analog input configuration switches based on the type of output signal. For speed control using PLC or BMS
with an independently powered signal you will use 53 or 54 as the input signal, and 55 for the common.
Signal Type
Location
Dip Switch
4-20 mA
Analog Input 53
Dip Switch is in correct
position
0-10 VDC
Analog Input 54
Dip Switch is in correct
position
Fixed Speed
No AI input used
Digital Input 18 used for
start/stop
Please determine how you are going to setup
and program from one of three different
configurations below:
FIGURE 2 Analog Input Dip
Switches. (A54 is only selectable)
U: 0-10 VDC I: 4-20MA
Switches are located behind the keypad
FIGURE 1
Connections for
external speed signal