PAGE 27
Aquavar IPC Start-Up Genie
CentriPro
• Selecting English
US
• Change your
Setup Selection to
Application
• Change to Speed
Control
Please acknowledge
that the drive will
require an external
source and that have
your jumper wire on
DI18 on the next two
screens.
Now select your
Speed Reference
Source:
• Analog Input 53
for 0-20 MA Input
Application.
• Analog Input 54
for 0-10V DC Input
Application.
• No function for
on Fixed Speed
Application.
• The next two
screens will verify
that you have your
dip switches setup
correctly.
• Input your Motor
low reference
value (0) and High
reference Value
(60.0). This is
the scaling from
your input signal,
either a 4-20MA or
0-10VDC.
• For either a 4-20MA
or 0-10VDC
application please
select Minimum
speed at 0 Hz and
Maximum speed to
60 Hz.
• For fixed speed
application with no
input please select
the same minimum
and maximum
speed to have your
motor run.
• Press Ok to confirm
your Speed
configuration is
setup correctly.