PAGE 13
Aquavar IPC Start-Up Genie
CentriPro
✔
Select 10 Seconds for Flow Check High
Time.
✔
Select Enable for No Flow Power Calibration.
WARNING: The No Flow Power Calibration
Process requires the pump to be operated at
no flow. This can produce high pressure within
the system. Ensure the system piping and
components are designed to withstand the
suction pressure plus shutoff head pressure
produced by the pump prior to starting the
calibration process.
✔
Follow all onscreen instructions carefully.
✔
Close outlet valve before starting
✔
The drive will now run through steps 1-4.
✔
Once the calibration is completed, select
OK and the down arrow to proceed.
Run Some Production and verify that the
drive is starting and cycling into sleep or
standby mode.
If you are having difficulty, please refer to the
AQIPCQA IPC Troubleshooting guide at the
end of this guide.