PAGE 16
Aquavar IPC Start-Up Genie
CentriPro
WIRING PREPARATION
Ensure that Start-Up Genie is complete. You can now prepare wiring for:
Jumpers on BOTH drives
Transducers on BOTH drives
Wiring Harness to connect BOTH drives
Duplex cable part # 9K706 (3 ft) or
#9K707 (6 ft)
DIP SWITCH SELECTION
• Simplex: Requires no action. Dipswitch is correct
position for 4-20MA Transducer Feedback.
• Duplex: Requires Analog 54
dipswitch to be moved over on
BOTH drives. To move dip switch
follow these instructions:
1. Remove Keypad
2. Carefully move Dipswitch A54 to the right to the
“I” position on BOTH drives. Please use care and
do not break the switch. Move it until you hear it
click into position.