19. QUESTION
Why am I getting an A-2 fault?
19. ANSWER
Verify that your pressure transducer is wired
correctly. Brown is on terminal #12 (24V), White
is on terminal #53 (4-20MA). Place ground shield
between spring clip and shielded cable.
20. QUESTION
My display is dark and not illuminated
20. ANSWER
Verify incoming power, and also check that the
panel is set into its connector all the way. You can
adjust the contrast on the LCP by pressing “Status” +
up/down arrow.
21. QUESTION
My display is not showing PSI set point and actual
PSI.
21. ANSWER
Cycle through the display options simply by using
the up and down arrows until your desired data is
displayed on the LCD.
22. QUESTION
How do I change my set point?
22. ANSWER
Simply by selecting quick menu, my personal menu,
and then inputting your desired PSI here.
23. QUESTION
The drive is constantly restarting once it cycles off.
23. ANSWER
Please check your system for leaks, a faulty check
valve (required), bladder tank setting (20 PSI below
your shutoff), or a constant demand. You can also
adjust the restart difference in the startup Genie for
longer cycle times.
24. QUESTION
Is there a way I can reset the drive back to factory
defaults?
24. ANSWER
Yes. Simply power off the drive, hold down the
status, Main menu, and OK, buttons while re-
applying power. Do not let go until you see
initializing come on to the display. You can then let
go and wait until it re-sets. Go back and reprogram
in your startup Genie.
You can also go to Main Menu, Go to Menu 14-22,
operation mode, and select Initialization. Then cycle
your power off.
25. QUESTION
My drive is going into sleep mode as soon as it
reaches the set point.
25. ANSWER
Please verify that you have run your No Flow Power
calibration. If you have not, go into the Genie and
Select Pump Protection and follow the on screen
prompts. Once you have completed this please try
run some cycles to see if this remedies.