PAGE 21
Aquavar IPC Start-Up Genie
CentriPro
NO FLOW POWER CALIBRATION
Select 10 Seconds for Flow Check High Time.
Select Enable for No Flow Power Calibration.
Follow all on-screen instructions carefully.
WARNING: The No Flow Power Calibration
Process requires the pump to be operated at
no flow. This can produce high pressure within
the system. Ensure the system piping and
components are designed to withstand the
suction pressure plus shutoff head pressure
produced by the pump prior to starting the
calibration process.
Close outlet valve before starting.
The drive will now run through steps 1-4.
Once the calibration is completed select OK
and the down arrow to proceed.