Warning Messages
975-0390-01-01
47
Error Code
Condition
Mode
Action
E10
High battery voltage (> 15.5 V)
AC shore power
Check for external charging sources, such as an over voltage
alternator, and disconnect if necessary.
Confirm that the external charging source is not the cause. The error may
be caused by the internal battery charger system. Call Xantrex for support.
E11
Over-temperature detected on
the AC transfer relay
AC shore power
Reduce the loads connected to the AC outlet of the unit.
Check that the ventilation grille is not blocked.
Check for ambient temperature and move the unit to a cooler location
whenever possible.
E12
Battery is bad or external DC load
is connected to the battery.
AC shore power
Check the battery bank.
NOTE: The battery voltage did not rise above 5 volts DC after 1 minute or 10
volts DC after 15 minutes.
Check that the external DC load current consumption is below the charging
current setting.
Disconnect the DC load or increase the charger current setting.
For error code
E01
:
n
the display screen and the alarm will turn off after 30 seconds
a
n
after a five-minute shutdown delay
b
, the unit will immediately
stop inverting
For error code
E12
:
n
the unit will stop charging and shut down, and
n
the error code will show on the display screen briefly, and
n
AC power will not pass through to the AC outlets.
For error codes
E02
to
E04
: the unit will stop inverting.
a
Available in all models (including some PN: 806-1840-01) except Freedom HF 1500 and 1800 T.
b
Available only for the Freedom HF 1500 and 1800 T models.