Parameterization
93
Then the display shows:
With
enter the parameterization level.
Parameterization of recorder outputs Rec 1 and Rec 2
(ST / R / RS models)
This submenu allows to set current range 0 .. 20 mA / 4 .. 20 mA and
response d
II
/t (d
II
= change of current; t = time).
Chart:
Submenu
PARA REC 1 or PARA REC 2
0..20 mA
Current range
4..20 mA *)
1
In this submenu
d
II
/t=
0.1 mA/s
Response
1)
characteristic
one parameter
d
II
/t=
0.2 mA/s
has to be selected out of
d
II
/t=
0.5 mA/s
1 current range part
d
II
/t=
1 mA/s
2
and also one out of
d
II
/t=
2 mA/s
2 response part.
d
II
/t=
5 mA/s
d
II
/t=
10 mA/s
d
II
/t=
20 mA/s *)
*) ex-factory condition
1)
Response: Changing velocity of the recorder current in milliampere per second with
erratic change of input signal (delta [
II
] per time unit [t]).
Setting:
Submenu "PARA REC 1"
With
enter submenu
"PARA REC 1".