COMMISSIONING
6 720 648 726 (2011/07)
54
B
Press the "Chimney sweep" button (
Æ
until the dot disappears from the display.
B
Switch off the heating system by pressing the mains
switch of the BC10 basic controller (
Æ
B
Close the gas valve (
Æ
fig. 81, page 50).
B
Remove the measuring devices.
B
Tighten the screw in the burner pressure measuring
nipple.
B
Slowly open the gas valve by pushing on the gas valve
and turning it ¼ rotation in an anticlockwise direction
(
Æ
B
Switch on the heating system by pressing the mains
switch of the BC10 basic controller (
Æ
B
Press and hold the "Chimney sweep" button
(
Æ
fig. 90, [3]) (approx. 2 seconds), until the dot in
the right-hand bottom corner of the display
(
Æ
fig. 90, [9]) appears. See also table 10, "Flue gas
test", page 42.
B
After the "Burner" LED (
Æ
fig. 90, [6]) has lit up wait
for one minute until the boiler is burning at full load.
B
Press the "Chimney sweep" button (
Æ
fig. 90, [3]) to
clear the reading. See also table 10, "Flue gas test",
page 42.
B
Check that the boiler performance is still at the
required value. See table 13 „"Settings", page 45.
10.2.8 CARRYING OUT A LEAKAGE TEST IN
OPERATING CONDITIONS
B
Press and hold the "Chimney sweep" button [3]
(approx. 2 seconds), until the dot in the right-hand
bottom corner of the display [9] appears. See also
table 10, "Flue gas test", page 42.
B
After the "Burner" LED [6] has lit up wait for one
minute until the boiler is burning at full load.
B
Use a foaming product to check all sealing locations
in the total gas circuit of the burner while the burner
is active.
B
Press the "Chimney sweep" button [3] to clear the
reading. See also table 10, "Flue gas test", page 42.
Fig. 90 BC10 basic controller
DANGER:
Danger of fatal accident from
explosive fumes.
B
Check the testing nipples used for gas
tightness.
B
Only use approved leak detection
products to locate leaks.
WARNING:
Damage to the installation due to short
circuits.
B
Cover any hazardous locations prior to
locating the leaks.
B
Do not spray the leak detection product
on cable runs, plugs or electrical wiring.
Do not let it drip onto them either.
DANGER:
Danger of fatal accident from
explosive fumes.
Pipes and fittings may leak after
commissioning activities have been carried
out.
B
Only use approved leak detection
products to locate leaks.
WARNING:
Damage to the installation due to short
circuits.
B
Cover any hazardous locations prior to
locating the leaks.
B
Do not spray the leak detection product
on cable runs, plugs or electrical wiring.
Do not let it drip onto them either.
888
1
10
9
8
7
6
5
4
3
2
1
6 720 648 726-069.1TD
11