OPERATION
6 720 648 726 (2011/07)
40
9
OPERATION
9.1
GENERAL ITEMS
The boiler is fitted with a control unit, the BC10 basic
controller. This controller can be used to control the
heating system.
B
Push on the control panel to open it.
Fig. 68 Opening the control panel
The BC10 basic controller is located on the left, behind
the door (
Æ
fig. 1, [4]).
The BC10 basic controller consists of the following
components:
Fig. 69 BC10 basic controller
1
Mains switch
2
"Reset" button
3
"Chimney sweep" button
4
"Service" button
5
Service Connector
6
"Burner" LED (On/Off)
7
"Heat demand" LED
8
Maximum CH flow temperature dial
9
Display
10
DHW temperature dial
11
"DHW mode" LED
MAINS SWITCH
The mains switch [1] is used to switch the boiler on and
off.
"RESET" BUTTON
If a fault has occurred you may have to restart the boiler
by pressing the "Reset" button [2]. This is only required
in the event of a "locking" fault. "Blocking" faults are
reset automatically as soon as their cause has been
corrected. The display shows
[\/r/e|
during the reset
operation.
"CHIMNEY SWEEP" BUTTON
The "Chimney sweep" button ([3] is used to put the
boiler into flue gas test, service or manual operation
mode.
The flue gas test enables the boiler to be run in full-load
operation manually for a short period. See table 10,
"Flue gas test", page 42.
The service mode enables the boiler to be run in part-
load operation manually for a short period.
Measurements and settings are carried out on the boiler
during service mode. See table 11, "Service mode",
page 43.
Manual operation mode enables the boiler to be
operated manually for a long period. The boiler is
switched to manual mode when the control system has
not been installed yet or is out of order. See table 12,
"Manual operation", page 44.
A maximum heating water temperature in accordance
with the setting of the "Maximum heating water
temperature" dial [8] on the BC 10 basic controller
applies during chimney sweep, service and manual
operation.
6 720 648 726-044.1TD
888
1
10
9
8
7
6
5
4
3
2
1
6 720 648 726-069.1TD
11
If the boiler stops due to a fault again after
resetting the fault, the fault can be
remedied using the Service instructions.
Contact Worcester if necessary. See the
back of this document for contact details.
WARNING:
Damage to the installation with underfloor
heating: by the floor being overheated.
B
Limit the maximum CH flow temperature
using the "Maximum CH flow
temperature" dial [8] to the maximum
flow temperature of the floor heating
circuit (usually maximum 40 °C).