OPERATION
6 720 648 726 (2011/07)
42
Normal operation menu
Step 1
[\/2/4|
Display value. Currently measured CH flow temperature in °C.
Also see section 14.2, page 70.
Step 2
Continue in Normal operation menu?
Yes:
Æ
step 3
No:
Æ
step 1
Step 3
Press the
e
button.
Step 4
[p/1.6|
Display value. Currently measured system pressure in bar.
Also see section 14.2, page 70.
Step 5
Press the
e
button.
Step 6
[-/h/\|
Random display code. In this case: Operating phase: Boiler in heating
mode. Also see section 14.3, page 71.
Step 7
Have at least 5 seconds passed without a button being pressed and/or has the
mains voltage been interrupted ?
Yes:
Æ
step 1
No:
Æ
step 8
Step 8
Press the
e
button.
Æ
step 1
Table 9
Normal operation
Flue Gas Test menu
Step 1
[\/2/4|
Display value. Currently measured CH flow temperature in °C.
Also see section 14.2, page 70.
Step 2
Activate flue gas test?
Yes:
Æ
step 3
No:
Æ
step 1
Step 3
To activate the flue gas test:
Press and hold the
d
button for more than 2 but not longer than 5 seconds
Step 4
[\/2/4]
Display value. As soon as a non-flashing dot is shown in the right-hand
bottom corner of the display, the flue gas test has been activated. This
means that the boiler is in heating mode at a capacity of 100 % for a
maximum of 30 minutes. The maximum CH flow temperature as set on the
maximum CH flow temperature dial of the BC10 basic controller now
applies. DHW mode is possible during manual operation.
Step 5
Press the
e
button.
Step 6
[p/1.6|
Display value. Currently measured system pressure in bar.
Also see section 14.2, page 70.
Step 7
Press the
e
button.
Step 8
[-/a/\]
Display code: Operating phase: The boiler is in flue gas test mode.
Also see section 14.3, page 71.
Step 9
Press the
e
button.
Step 10
[\/2/4]
Display value. Currently measured CH flow temperature in °C.
Also see section 14.2, page 70.
Step 11
Have 30 minutes passed or has the mains voltage been interrupted?
Yes:
Æ
step 1
No:
Æ
step 12
Step 12
Deactivate flue gas test?
Yes:
Æ
step 13
No:
Æ
step 5
Step 13
To deactivate the flue gas test:
Press and hold the
d
button for more than 2 seconds until the dot disappears.
Æ
step 1
Table 10 Flue gas test