14.3 BC10 DISPLAY SETTINGS
14.4 BC10 DISPLAY CODES
Display settings
Display
setting
Meaning of display setting
Unit
Range
Factory
adjusted
setting
[l/9/9|
Configured target load (65 kW).
%
[l/2/0|
–
[l/9/9|
/
[l/-/-|
100 %
[l/-/-|
[l/9/9|
Configured target load (80 kW).
%
[l/2/5|
–
[l/9/9|
/
[l/-/-|
100 %
[l/-/-|
[l/9/9|
Configured target load (100 kW).
%
[l/2/0|
–
[l/9/9|
/
[l/-/-|
100 %
[l/-/-|
[f/\.5|
Configured target value of the
pump run-over time.
Note: Do not set a pump
run-over time of less than
[f/\/5|
(= 5 minutes).
min.
[f/0/0|
–
[f/6/0|
/
[f/1/d|
24 h
[f/\/5|
[c/\.1|
DHW supply operating condition
setting.
Please note: If the setting
[c/\/0|
is
displayed, the frost protection of
the DHW supply has also been
switched off.
not
appli-
cable
[c/\/0|
Off
/
On
[c/\/1|
Table 23 Display settings
Display codes
Display code
LED on
UBA 3
Other effects
z
Main
display
code
z
Sub
display
code
z
Key to display code
Reset
requi-
red?
[\/-/\|
Operating phase:
Communication test while starting up. This
display code flashes 5 times within
5 seconds while starting up to indicate that
the communication between the UBA 3 and
the BC10 basic controller is being tested. If
a new UBA 3 or a new KIM was fitted, this
code will flash for max. 10 seconds.
Off or
flashing
at 8 Hz
[\/-/\|
Fault:
If this code continues to flash on the display,
there is a fault in the communication
between the UBA 3 and the BC10 basic
controller.
Off or
flashing
at 8 Hz
e
[-/a/\]
1)
e
[2/0/8|
2)
Operating phase:
The boiler is in flue gas test or service mode.
Off or
flashing
at 8 Hz
No heating operation
and no DHW.
e
[-/h/\|
e
[2/0/0|
Operating phase:
The boiler is in heating mode.
Off
Table 24 Display codes