Service Mode menu
Step 1
[\/2/4|
Display value. Currently measured CH flow temperature in °C. Also see
section 14.2, page 70.
Step 2
Activate service mode?
Yes:
Æ
step 3
No:
Æ
step 1
Step 3
To activate service mode 1st step:
Press and hold the
d
button for more than 2 but not longer than 5 seconds
Step 4
[\/2/4]
Display value. As soon as a non-flashing dot is shown in the right-hand
bottom corner of the display, the boiler is in heating mode at a capacity of
100 % for a maximum of 30 minutes. The maximum CH flow temperature
as set on the maximum CH flow temperature dial of the BC10 basic
controller (control panel) now applies.
Step 5
To activate service mode 2nd step:
Simultaneously press and hold the
d
+
e
buttons for more than 2 seconds.
Step 6
[l/-/-]
Display setting. Maximum capacity setting during heating mode in %.
Also see section 14.3, page 71. In this case:
[l/-/-]
= 100 %. Service mode
has been activated. You can now temporarily lower the boiler performance
to partial load to check and if relevant set the gas/air ratio or the
ionisation current.
Step 7
Press and hold the
c
button until the display shows
[l/2/5]
with a 80-kW boiler or
[l/2/0]
with a 65 and 100-kW boiler.
Step 8
[l/2/5]
Display setting: with a 80-kW boiler and
[l/2/0]
with a 65 and 100-kW boiler.
Minimum capacity setting during heating mode in %. Also see
section 14.3, page 71. The boiler will reduce its performance to 25 % or
20 % respectively within a couple of seconds. The maximum CH flow
temperature set on the BC10 basic controller (control panel) applies now.
Check the gas/air ratio or the ionisation current and if necessary set the
gas/air ratio according to subsection 10.2.7 or subsection 10.2.11.
Step 9
Press the
e
button.
Step 10
[f/\/5|
Display setting: This parameter shows the pump run-over time in minutes
when heating mode has been ended. Also see section 14.3, page 71.
Step 11
Press the
e
button.
Step 12
[c/\/1|
Display setting: This parameter indicates the DHW mode status setting.
Also see section 14.3, page 71.
.
Step 13
Press the
e
button.
Step 14
[\/2/4|
Display value. Currently measured CH flow temperature in °C.
Also see section 14.3, page 71.
Step 15
Press the
e
button.
Step 16
[p/1.6|
Display value. Currently measured system pressure in bar.
Also see section 14.3, page 71.
Step 17
Press the
e
button.
Step 18
[-/a/\|
Display code: Operating phase: The boiler is in service mode.
Also see section 14.3, page 71.
Step 19
Press the
e
button.
Table 11 Service mode