OPERATION
6 720 648 726 (2011/07)
45
Step 11
Has there been a power failure?
Yes:
Æ
step 1
No:
Æ
step 12
Step 12
Deactivate manual operation?
Yes:
Æ
step 13
No:
Æ
step 5
Step 13
To deactivate manual operation:
Press and hold the
d
button for more than 2 seconds until the dot disappears.
Æ
step 1
Settings menu
Step 1
[\/2/4|
Display value. Currently measured CH flow temperature in °C.
Also see section 14.2, page 70.
Step 2
Open the “Settings” menu?
Yes:
Æ
step 3
No:
Æ
step 1
Step 3
To open the "Settings" menu:
Press and hold the
d
+
e
buttons for more than 2 seconds
Step 4
[l/-/-]
Display setting. As soon as the display shows
[l/-/-]
, the "Settings" menu
is open. You can set the boiler performance using the first parameter
shown on the display. Also see section 14.3, page 71.
Step 5
Adjust boiler performance?
Yes:
Æ
step 7
No:
Æ
step 6
Step 6
Lower: Decrease the target boiler output with the
c
button. The minimum setting
is
[l/2/5]
= 25 % with an 80-kW boiler and
[l/2/0]
= 20 % with a 65 and 100-kW boiler.
Higher: Increase the target boiler output with the
d
button. The maximum setting
is
[l/-/-]
= 100 %. This is equal to the factory setting.
Step 7
Press the
e
button.
Step 8
[f/\/5|
Display setting: Set the second parameter as soon as the display shows
[f/\/5|
. This parameter shows the target pump run-over time in minutes
after heating operation has ended. Also see section 14.3, page 71.
Note: Do not set a pump run-over time of less than
[f/\/5|
(= 5 minutes).
Step 9
Set the pump run-over time after heating operation has ended?
Yes:
Æ
step 10
No:
Æ
step 11
Step 10
Lower: Decrease the target pump run-over time after the end of heating operation
with the
c
button. The minimum setting is
[f/\/0|
= 0 minutes. The factory default
setting is 5 minutes. CAUTION: Do not set the target pump run-over time after the
end of heating operation to less than 5 minutes.
Higher: Increase the target pump run-over time after the end of heating operation
with the
d
button. The maximum setting is
[f/6/0|
= 60 minutes or
[f/1/d|
= 24 hours.
Step 11
Press the
e
button.
Table 13 Settings
Manual operation menu
Table 12 Manual operation