Power Factor Sharing
When either VAR or Power Factor Control is selected, and the DSLC control is
operating in isochronous load sharing mode, power factor sharing is
automatically selected. Power factor sharing adjusts the voltage regulators so
that all generators carry the same proportion of reactive load by balancing the
power factor on all units. A voltage reference set point is provided to define the
system operating voltage. If enabled, the voltage trim function will maintain the
bus voltage to the voltage reference plus-or-minus the voltage regulation
percentage.