
DSLC Digital Synchronizer and Load Control
Manual 02007
32
Woodward
30.
Reverse Pwr Level and Rev Pwr Time Delay
are used to determine the
time delay before energizing the load switch output when the generator is
being motored, and the Reverse Power Trip is enabled.
Menu 3—Process Control
1.
Process Control Gain
determines how fast the process control responds to
an error between the process variable and reference. The gain is set to
provide stable control of the process.
2.
Process Stability
compensates for delay in the process control loop. It
prevents low frequency hunting and damping (overshoot or undershoot)
when a process disturbance occurs.
3.
Process Derivative
adjusts the rate of change in speed bias output during
a process level transient.
4.
Process Deadband
is the error window within which the process control
integrator is not updated. This is used for control of high noise processes.
Set to 0.0 mA for normal, non-deadband control.
5.
Process Droop
is the load droop desired based on process level.
6.
Process Filter
adjusts the bandwidth of the filter on the process input.
Higher frequency settings result in faster control response, but also more
response to process noise.
7.
Process Reference
is the internal reference for the process control.
8.
Raise Reference Rate
is the rate at which the process reference is
increased when the raise command input is activated.
9.
Lower Reference Rate
is the rate at which the process is decreased when
the lower command input is activated.
10.
High Limit PU
is the process input level where (if enabled) the High Limit
discrete output is energized and the high limit alarm is activated. The High
Limit PU set point also limits the maximum process reference setting.
11.
High Limit DO
is the process input level where (if enabled) the High Limit
discrete output is de-energized and the high limit alarm deactivated.
12.
High Limit Alarm
specifies if the process high limit alarm will activate (de-
energize) the alarm driver, terminal 28.
13.
Low Limit PU
is the process input level where (if enabled) the Low Limit
discrete output is energized and the low limit alarm is activated. The Low
Limit PU set point is also the minimum process reference setting.
14.
Low Limit DO
is the process input level where (if enabled) the Low Limit
discrete output is de-energized and the low limit alarm deactivated.
15.
Low Limit Alarm
specifies if the low limit alarm will activate (de-energize)
the alarm driver, terminal 28.
16.
Process Switches
specifies if the High and Low Limit discrete outputs,
terminals 26 and 27, will activate on high or low process alarm.