Finally, use the “SAVE” key to save entered values. After you are satisfied with
all entries and adjustments, press the “SAVE” key to transfer all new set point
values into EEPROM memory. The EEPROM retains all set points when power
is removed from the control.
CAUTION—SAVE SET POINTS
To prevent possible damage to the engine resulting from improper control
settings, make sure you save the set points before removing power from the
control. Failure to save the set points before removing power from the
control causes them to revert to the previously saved settings.
The control ignores all other keys on the Hand Held Programmer.
Min. Max. Initial Dimen-
Name
Value Value Value sion
Menu 1—Synchronizer
1. Sync
Gain
0.01
100.0
0.10
2. Sync
Stability
0.00 20.00 1.00 seconds
3.
Slip
Frequency
Ref 0.00 0.25 0.05 Hz
4.
Slip
Window
0.00 1.00 0.05 Hz
5.
Max Phase Window
2
20
10
degrees
6. Voltage
Matching
Enabled/Disabled
Enabled
7.
Voltage
Window
0.0 10.0 1.0 %
8. Dead-bus
Closure
Enabled/Disabled
Disabled
9. Breaker
Delay
0.00 2.00 0.10 seconds
10.
CB Close Hold Time
0.0
5.00
1.0
seconds
11. Close
Attempts
1
20
1
12. Reclose
Delay
1
1000
20
seconds
13.
Sync Reclose Alarm
Enabled/Disabled
Enabled
14.
Sync
Timeout
0 1000
0 seconds
15.
Sync Timeout Alarm
Enabled/Disabled
Disabled
16. Auto
Re-Synchronize
Enabled/Disabled
Disabled
Menu 2—Load Control
1.
Load Control Gain 0.0001
100.0000
0.2500
2. Load
Stability
0.00
20.00 1.00 seconds
3.
Load
Derivative
0.00 20.00 0.00 seconds
4.
Load Control Mode
Integrating/Proportional Proportional
5.
Load Control Filter 0.1 10.0 1.0 Hz
6.
Loadshare
Gain
0.10 2.00 0.72
7. Frequency
Trimmer
Enabled/Disabled
Disabled
8.
Rated Load
0
30 000
1000
kW
9.
Base Load
0
30 000
1000
kW
10.
Unload Trip
0
30 000
0
kW
11.
Load
Droop
0.0 100 5.0 %
12. Load
Time
1
7200
20
seconds
13. Unload
Time
1
7200
20
seconds
14.
Raise Load Rate
0.01 100.00
1.00 %/sec
15.
Lower Load Rate
0.01 100.00
1.00 %/sec
16.
4mA Remote Load
0
30 000
0.0
W,kW,MW
17.
20mA Remote Load
0
30 000
1000
W,kW,MW
18.
High Limit PU
0
30 000
1000
W,kW,MW
19.
High Limit DO
0
30 000
900
W,kW,MW
20.
High Limit Alarm
Enabled/Disabled
Disabled
21.
Low Limit PU
30 000
30 000
10
W,kW,MW
22.
Low Limit DO
30 000
30 000
10
W,kW,MW
23.
Low Limit Alarm
Enabled/Disabled
Disabled
24.
Load Limit Switches
Enabled/Disabled
Disabled
25.
Load Switch PU
30 000
30 000
300
W,kW,MW
26.
Load Switch DO
30 000
30 000
200
W,kW,MW
27.
Reverse Power Trip
Enabled/Disabled
Disabled
28.
Instant Reverse Power
50.0
1.0
10 %
load
29.
Rev Pwr Time Delay
0.1
20.0
20.0
seconds
30.
Reverse Power Level
50.0
1.0
1.0 %
load