
DSLC Digital Synchronizer and Load Control
Manual 02007
38
Woodward
12.
Process Switch
is the status of the Process Control Mode select input.
13.
Test Key
must be set to “49”, generator voltage must be below 40 Vac L-N,
and the discrete inputs must all be open, to allow closing of discrete outputs
for test purposes.
14.
Breaker Close Relay
is the status of the Circuit Breaker Closure Command
Relay.
15.
Breaker Open Relay
is the status of the Circuit Breaker Open Command
Relay.
16.
Voltage Raise Relay
is the status of the Voltage Raise Command Relay.
17.
Voltage Lower Relay
is the status of the Voltage Lower Command Relay.
18.
High Limit Relay
is the status of the High Limit Switch Relay.
19.
Low Limit Relay
is the status of the Low Limit Switch Relay.
20.
Load Switch Relay
is the status of the Load Switch Relay.
21.
Alarm Relay
is the status of the Alarm Relay.
22.
Sync Enable LED
is the status of the Sync Enable LED.
23.
High Limit LED
is the status of the High Limit LED.
24.
Low Limit LED
is the status of the Low Limit LED.
25.
CPU OK LED
is the status of the CPU OK LED.
Menu 0—Diagnostics
1.
Diagnostic Result
is the result of power up diagnostics. A value of 49
indicates no problems found. Any other value indicates an internal failure in
the microprocessor or memory.
2.
ROM Check Sum
is the result of doing a “checksum” test on program
memory. This value is verified each time the control is powered up. This
number is for factory test only. A failure in the ROM checksum test will also
result in a Diagnostic Result other than 49.
3.
Active DSLCs
is the number of DSLC controls currently powered on the
network. This value is used to verify that all DSLC controls in the network
are in communication with each other.
4.
Retrieve Net Status
retrieves the network error statistics accumulators, the
cause of the last reset, the state of the node, and the last run-time error
logged. Pressing the “.” key will retrieve the current statistics which can be
observed with the following set points.
Transmission errors will occur on occasion. Frequent occurrence of
transmission errors (that is, several per minute) indicates an overloaded
network, faulty network wiring, or a defective control in the network.
Status information is used during network installation to verify correct
operation.