DSLC Digital Synchronizer and Load Control
Manual 02007
24
Woodward
Min. Max. Initial Dimen-
Name
Value Value Value sion
Menu 3—Process Control
1. Process
Control
Gain 0.0001
100.0000
0.1000
2. Process
Stability
0.00 20.00 1.00 seconds
3. Process
Derivative 0.00 20.00 0.00 seconds
4.
Process
Deadband 0.00 20.00 0.10 mA
5.
Process
Droop
0.0 100.0
0.0 %
6. Process
Filter
0.1 5.0 1.0 Hz
7. Process
Reference 0.0 20.0 12.0 mA
8.
Raise Reference Rate
0.01 20.00 0.10 mA/sec
9.
Lower Reference Rate
0.01 20.00 0.10 mA/sec
10.
High Limit PU
0.0
25.0
15.0
mA
11.
High Limit DO
0.0
25.0
15.0
mA
12.
High Limit Alarm
Enabled/Disabled
Disabled
13.
Low Limit PU
0.0
25.0
10.0
mA
14.
Low Limit DO
0.0
25.0
10.0
mA
15.
Low Limit Alarm
Enabled/Disabled
Disabled
16. Process
Switches
Enabled/Disabled
Disabled
Menu 4—VAR/Power Factor Control
1.
VAR/PF Control Mode
Disabled/
Disabled
PF
Control/
VAR
Control
2. VAR/PF
Gain
0.01
22.00
1.00
3. VAR/PF
Stability
0.00 20.00 2.50 seconds
4.
Rated KVARs
0
30 000 (gen.) 100
kVAR
5.
KVAR Reference
30 000 (abs.) 30 000 (gen.) 20 (gen.)
kVAR
6.
PF Reference
0.00 lagging 0.00 leading 0.8 lagging
7.
PF
Deadband
0.000 1.000 0.025
8. Voltage
Reference
50.0
300xPT
ratio 70xPT ratio V (L-L,L-N)
9. Voltage
Trim
Enabled/Disabled
Disabled
10. Voltage
Regulation 1.0 10.0 2.0 %
11.
Voltage Low Limit
50
300xPT ratio 60xPT ratio V (L-L,L-N)
12.
Voltage Low Alarm
Enabled/Disabled
Disabled
13.
Voltage High Limit
50
300xPT ratio 80xPT ratio V (L-L,L-N)
14.
Voltage High Alarm
Enabled/Disabled
Disabled
15. Voltage
Switches
Enabled/Disabled
Enabled
16.
Voltage Range Alarm
Enabled/Disabled
Disabled
17.
Voltage Ramp Time
1
600
60
seconds
Menu 5—Configuration
1. Configuration
Key
0
100
0
2.
PT Winding Ratio 1:1
1000.0:1
1.0:1
3.
CT Rating
5:5
10 000:5
5:5
4.
PT Voltage Input
120/240
120
5.
Voltage Display
V (L-L), V (L-N)
kV (L-L), kV (L-N) V (L-N)
6. System
Frequency
50/60
60
Hz
7.
Process Control Action
Direct/Indirect Indirect
8.
Network Address
1
16
0 (unconfigured)
9.
Network Service Pin
transmits unique ID code to network
Menu 6—Calibration
1. Calibration
Key
0
100
0
2. Process
Input
0
22
n/a
mA
3. Remote
Input
0
22
n/a
mA
4.
Speed Bias Output
100 +100
n/a %
5.
Voltage Bias Output
100 +100
n/a %
6.
PT Phase A
0
300
n/a
volts
7.
PT Phase B
0
300
n/a
volts
8.
PT Phase C
0
300
n/a
volts
9.
CT Phase A
0
7xCT rating n/a
amperes
10.
CT Phase B
0
7xCT rating n/a
amperes
11.
CT Phase C
0
7xCT rating n/a
amperes
12. Bus
Voltage
0
300
n/a
volts
13. Synchroscope
57.3 +57.3
n/a degrees