Table 4-11. General Configuration (4/9) Screen Command Buttons and Parameters
Use Baseload Control
TRUE
Visibility: Always
Select if baseload mode will be used.
CONFIGURATION MODE REQUIRED
User Level: Configure
Use Level Control
FALSE
Visibility: Always
Select if level control mode will be used.
CONFIGURATION MODE REQUIRED
User Level: Configure
Use Remote Baseload Control
FALSE
Visibility: Always
Select if remote baseload control mode will be used.
CONFIGURATION MODE REQUIRED
User Level: Configure and Use
Baseload Control enabled
Use Remote Level Control
FALSE
Visibility: Always
Select if remote level control mode will be used.
CONFIGURATION MODE REQUIRED
User Level: Configure and Use
Level Control enabled
Use Remote Speed Control
FALSE
Visibility: Always
Select if remote speed control mode will be used.
CONFIGURATION MODE REQUIRED
User Level: Configure
Speed Bias Type
NOT USED
Visibility: Always
Select type of speed bias will be used. The options are Not
used, Analog Input or Discrete Input.
CONFIGURATION MODE REQUIRED
User Level: Configure
Speed Bias Only for Synch
FALSE
Visibility: Always
Select if the speed bias will be used only for synch. If unselect
the speed bias will work all time.
CONFIGURATION MODE REQUIRED
User Level: Configure
Speed Bias Rate
0.1 (0.01, 1.0) %/s
Visibility: Always
Rate that Speed Bias control will ramp to increase or decrease
the speed reference
User Level: Service
Speed Bias Range
5.0 (1.0, 10.0) %
Visibility: Always
Range to be used by the speed bias. For example, if the range is
configured to 5% than the bias will vary between -5% and +5%.
If Speed Bias is configured for analog input 4mA will be -5%,
12mA will be 0% and 20mA will be +5%.
User Level: Service
The operator can navigate between the general configuration screens pressing the soft keys with arrows
to left or right.
Released
Summary of Contents for 505HT
Page 23: ...Manual 35116 505HT for Pelton Turbines Woodward 21 Figure 2 2 505D Outline Drawing Released...
Page 196: ...Manual 35116 505HT for Pelton Turbines Woodward 194 Figure F 10 Deflector Logic Released...
Page 197: ...Manual 35116 505HT for Pelton Turbines Woodward 195 Revision History New Manual Released...
Page 198: ...Manual 35116 505HT for Pelton Turbines Woodward 196 Declarations Released...