Manual 35116
505HT for Pelton Turbines
Woodward
70
Rate
0.5 (0.01, 10.0) %/s
Visibility: if specific nozzle is in use
Rate that the individual manual ramp will use to increase or
decrease the demand for the specific nozzle, when a pulse
command is issued or when the setpoint is changed by Modbus
command.
User Level: Service
Position Reference
Monitor
Visibility: if specific nozzle is in use
Shows the actual position reference for the specific nozzle.
User Level: N/A
Actual Position
Monitor
Visibility: if specific nozzle is in use
Shows the actual position of the specific nozzle.
User Level: N/A
Go to
Command
Visibility: Always
Command to send the individual manual setpoint to the “Go to
Value”.
User Level: Operator
Go to Value
0.0 (0.0, 100.0) %
Visibility: Always
Value where the individual manual demand goes when a “Go
to” command is issued.
User Level: Operator
Click on the “Test” button to go to the specific nozzle test page
Clicking on the left and right soft keys the operator will navigate between all nozzles’ manual control and
the individuals’ manual nozzle controls.
Nozzle Test Screen
The purpose of this screen is to provide a way to test the Nozzles individually.
Figure 4-10. Nozzle Test Screen
Released
Summary of Contents for 505HT
Page 23: ...Manual 35116 505HT for Pelton Turbines Woodward 21 Figure 2 2 505D Outline Drawing Released...
Page 196: ...Manual 35116 505HT for Pelton Turbines Woodward 194 Figure F 10 Deflector Logic Released...
Page 197: ...Manual 35116 505HT for Pelton Turbines Woodward 195 Revision History New Manual Released...
Page 198: ...Manual 35116 505HT for Pelton Turbines Woodward 196 Declarations Released...