Manual 35116
505HT for Pelton Turbines
Woodward
73
Table 4-6. Baseload Screen Command Buttons and Parameters
Rated Load
3.0 (0.0, 30000.0) MW
Visibility: Always
Enter the rated load of the generator in MW.
CONFIGURATION MODE REQUIRED
User Level: Configure
Maximum Baseload Reference
3.0 (0.0, 30000.0) MW
Visibility: Always
Enter the maximum baseload setpoint, when baseload is in
control. This value should be equal or less than the rated load
and equal or greater than the initial baseload reference.
User Level: Service
Initial Baseload Reference
0.5 (0.0, 30000.0) MW
Visibility: Always
Enter the initial baseload setpoint, this is the setpoint that the
control will assume when the baseload control is configured to
be the first control mode when generator breaker closes. This
value should be equal or less than the maximum baseload
reference and equal or greater than the minimum baseload
reference.
User Level: Service
Unload Level
0.5 (0.0, 30000.0) MW
Visibility: Always
Enter the unload level, this is the value where the control will
send the command to open the generator breaker (if used) and it
is also the value where the control goes when the unload
command is issued. This value should be equal or less than the
minimum baseload reference.
User Level: Service
Baseload Rate (Min to Max Load)
*60.0 (1.0, 600.0) s
Visibility: Always
Enter the time the control will spend to go from the minimum
baseload reference to the maximum baseload reference. This
value will be the rate of the baseload reference ramp.
User Level: Service
Remote Baseload Rate (Min to Max
Load)
*60.0 (1.0, 600.0) s
Visibility: Always
Enter the time the control will spend to go from the minimum
baseload to the maximum load reference when in remote
baseload control. Remote baseload is when the baseload
setpoint is following an analog input.
User Level: Service
Press the soft key “Commands” to go to the baseload commands screen.
Released
Summary of Contents for 505HT
Page 23: ...Manual 35116 505HT for Pelton Turbines Woodward 21 Figure 2 2 505D Outline Drawing Released...
Page 196: ...Manual 35116 505HT for Pelton Turbines Woodward 194 Figure F 10 Deflector Logic Released...
Page 197: ...Manual 35116 505HT for Pelton Turbines Woodward 195 Revision History New Manual Released...
Page 198: ...Manual 35116 505HT for Pelton Turbines Woodward 196 Declarations Released...