Manual 35116
505HT for Pelton Turbines
Woodward
13
Calibration Mode –
This mode is used to calibrate, tune and adjust certain parameters either while the unit is shutdown, or
during turbine run time. A password is required to log into this mode.
Operation Mode -
This mode is the typical state for normal operations of the control and the turbine. The Run Mode is used
to operate the turbine from start-up through shutdown.
505 Inputs and outputs
Control Inputs
Speed Input Signals
Two redundant speed inputs are configurable to accept MPUs (magnetic pickup units), or active proximity
probes.
Analog 4-20mA Input Signals
There are eight configurable analog inputs available on the 505 hardware, each of which can be
configured as one of the following input functions:
Table 1-1. Selectable functions for 4-20mA Analog Inputs
1- Not used
2- Pond / Tail level
3- Generator Power
4- Speed Bias
5- Remote Speed Reference
6- Nozzle Position Limiter
7- Remote Baseload reference
8- Remote level reference
9- Nozzle 1 Position feedback
10- Nozzle 2 Position feedback
11- Nozzle 3 Position feedback
12- Nozzle 4 Position feedback
13- Nozzle 5 Position feedback
14- Nozzle 6 Position feedback
Discrete Contact Input Signals
Twenty contact inputs are available. The first five inputs are dedicated for Run/Stop (DI-1), Raise
Speed/load (DI-2), Lower Speed/Load (DI-3), Breaker Closed (DI-4) and Emergency Shutdown (DI-5).
The next 4 channels are configurable as per the list below, but for convenience are defaulted to the
following functions: Deflector closed, Deflector Opened, Baseload Enable and Start Permissive. The rest
of the additional contact inputs are available for configuration to function as various controller discrete
input functions as listed below. On the front panel display there are 4 additional keys that are always
available for operational functions (GREEN keys) – Start/Stop/Reset and Adjust Up/Down for raising or
lowering a highlighted value.
Table 1-2. Selectable functions for Discrete Inputs
1- Not Used
2- Manual Nozzle Control Enable
3- Pond / Tail Level Control Enable
4- Nozzle Limit Raise
5- Nozzle Limit Lower
6- Creep input #1
7- Creep input #2
8- Reset
9- External Start Permissive
10- Speed Bias Raise
11 - Speed Bias Lower
12- Baseload Enable
13- Unload
14- Local / Remote
15- load droop Enable
16- Remote Fault #1
25- Manual Nozzle #4 Enable
26- Manual Nozzle #5 Enable
27- Manual Nozzle #6 Enable
28- Nozzle #1 Manual Raise
29- Nozzle #1 Manual Lower
30- Nozzle #2 Manual Raise
31- Nozzle #2 Manual Lower
32- Nozzle #3 Manual Raise
33- Nozzle #3 Manual Lower
34- Nozzle #4 Manual Raise
35- Nozzle #4 Manual Lower
36- Nozzle #5 Manual Raise
37- Nozzle #5 Manual Lower
38- Nozzle #6 Manual Raise
39- Nozzle #6 Manual Lower
40- Manual Deflector Enable
Released
Summary of Contents for 505HT
Page 23: ...Manual 35116 505HT for Pelton Turbines Woodward 21 Figure 2 2 505D Outline Drawing Released...
Page 196: ...Manual 35116 505HT for Pelton Turbines Woodward 194 Figure F 10 Deflector Logic Released...
Page 197: ...Manual 35116 505HT for Pelton Turbines Woodward 195 Revision History New Manual Released...
Page 198: ...Manual 35116 505HT for Pelton Turbines Woodward 196 Declarations Released...