Manual 35116
505HT for Pelton Turbines
Woodward
128
Speed Switch Screen
The purpose of this screen is to configure the Speed Switches. There are six speed switches available on
the 505.
Figure 4-49. Speed Switches Screen
Table 4-40. Speed Switches Screen Configuration Values
High Value
1.0 (0.0, 200.0) %
Visibility: Always
Enter the high value (in %) for the specific speed switch.
User Level: Service
High Delay
*0.0 (0.0, 600.0) s
Visibility: Always
Enter the high delay time for the specific speed switch.
User Level: Service
Low Value
0.5 (0.0, 200.0) %
Visibility: Always
Enter the low value (in %) for the specific speed switch.
User Level: Service
Low Delay
*0.0 (0.0, 600.0) s
Visibility: Always
Enter the low delay time for the specific speed switch.
User Level: Service
Decreasing Switch
FALSE
Visibility: Always
Select if the switch is a decreasing switch.
User Level: Service
Decreasing Switch
FALSE
Visibility: Always
Select to use fail safe condition.
User Level: Service