Manual 35116
505HT for Pelton Turbines
Woodward
131
High Delay
*0.0 (0.0, 600.0) s
Visibility: Always
Enter the high delay time for the specific speed switch.
User Level: Service
Low Value
0.5 (0.0, 200.0) %
Visibility: Always
Enter the low value (in %) for the specific speed switch.
User Level: Service
Low Delay
*0.0 (0.0, 600.0) s
Visibility: Always
Enter the low delay time for the specific speed switch.
User Level: Service
Decreasing Switch
FALSE
Visibility: Always
Select if the switch is a decreasing switch.
User Level: Service
Decreasing Switch
FALSE
Visibility: Always
Select to use fail-safe condition.
User Level: Service
Fail Safe State
OPEN
Visibility: Always
Choose the fail-safe condition in case of power transducer signal
fail.
User Level: Service
This switches has no time to disable, and will go back to its normal state when the power transducer
signal is working properly again.
The operator can navigate between the switches pressing the soft keys with arrows to left or right or go to
the other switches pressing the soft keys “Load switches” or “Speed Switches” (when available).