Manual 35116
505HT for Pelton Turbines
Woodward
134
There are three information at the top of the page: the signal (in mA), the actual value (in the configured
engineering unit) and if the signal is failed.
The default values showed below are for the analog input #1.
Table 4-43. Analog Inputs Screen Configuration Values
Function
NOZZLE 1 POS FDBK
Visibility: Always
Choose the function of the specific analog input.
CONFIGURATION MODE REQUIRED
User Level: Configure
4 mA Value
0.0 (-1.0e+38, 1.0e+38)
Visibility: Always
Set the value (in engineering units) that corresponds to 4
milliamps (mA) on the analog input.
User Level: Service
20 mA Value
100.0 (-1.0e+38, 1.0e+38)
Visibility: Always
Set the value (in engineering units) that corresponds to 20
milliamps (mA) on the analog input.
(Must be greater than the ‘Input 4 mA Value’ Setting)
User Level: Service
Loop Powered
FALSE
Visibility: Always
Check this box if the 505 should provide loop power for the
transmitter.
CONFIGURATION MODE REQUIRED
User Level: Configure
Device Tag
AI_01
Visibility: Always
This is a user entered field. It allows entry of a short description
or tag name for this channel.
User Level: Service
Units
AI 01 Units
Visibility: Always
This is a user entered field. It allows entry of a unit label for this
channel
User Level: Service
Modbus Multiplier
1
Visibility: Always
This is the multiplier that will be used for this parameter address
on the 505 slave Modbus communication link. The options are
(1, 10, 100 or 1000)
User Level: Service
The operator can navigate between the analog inputs pressing the soft keys with arrows to left or right.
Analog Inputs # 2 through # 8 are configured following the same rules as described for Analog Input # 1.
Entering Text
The Device Tag is a text field that is available for the user to enter a
unique name or identifier for each I/O channel. An example would be
to use the signal device tag such as NZ-1234 for an nozzle position
sensor. Enter Text characters by focusing on the field, press Enter,
then press and hold down the alphanumeric keys – they will cycle
through the available characters on that key
Calibrate the analog inputs pressing the soft key “Calibrate” and the below screen will open.
Released
Summary of Contents for 505HT
Page 23: ...Manual 35116 505HT for Pelton Turbines Woodward 21 Figure 2 2 505D Outline Drawing Released...
Page 196: ...Manual 35116 505HT for Pelton Turbines Woodward 194 Figure F 10 Deflector Logic Released...
Page 197: ...Manual 35116 505HT for Pelton Turbines Woodward 195 Revision History New Manual Released...
Page 198: ...Manual 35116 505HT for Pelton Turbines Woodward 196 Declarations Released...