Manual 35116
505HT for Pelton Turbines
Woodward
122
Communications (Serial Port) Screen
The purpose of this screen is to configure serial communication port.
Figure 4-45. Communications (Serial Port) Screen
Table 4-36. Communications (Serial Port) Screen Configuration Values
Use serial
FALSE
Visibility: Always
Select if the serial port communication will be used.
User Level: Service
Baud Rate
115200
Visibility: Always
Select the baud rate for the serial port, the options are: 110, 300,
600, 1200, 1800, 2400, 4800, 9600, 19200, 38400, 57600 and
115200.
User Level: Service
Data Bits
8
Visibility: Always
Select the data bits for the serial port, the options are: 7 and 8
User Level: Service
Stop Bits
1
Visibility: Always
Select the stop bits for the serial port, the options are: 1, 1.5 and
2.
User Level: Service
Parity
Off
Visibility: Always
Select the parity for the serial port, the options are: Off, Odd and
Even.
User Level: Service
Driver
RS-232
Visibility: Always
Select the driver for the serial port, the options are: RS-232, RS-
422 and RS-485.
User Level: Service
Released