Table 4-7. Baseload Commands Screen Command Buttons and Parameters
Enable
Command
Visibility: Always
This command will enable the baseload control mode.
User Level: Operator
Disable
Command
Visibility: Always
This command will disable the baseload control mode.
User Level: Operator
Lower
Command
Visibility: always
This command will lower the baseload reference.
User Level: Operator and if
baseload mode enabled
Raise
Command
Visibility: always
This command will raise the baseload reference.
User Level: Operator and if
baseload mode enabled
Rate (Min to Max)
*60.0 (1.0, 600.0) s
Visibility: Always
Enter the time the control will spend to go from the minimum
baseload reference to the maximum baseload reference. This
value will be the rate of the baseload reference ramp.
User Level: Service
Go to
Command
Visibility: Always
Command to send the baseload setpoint to the “Go to Value”.
User Level: Operator
Go to Value
0.0 (0.0, 100.0) %
Visibility: Always
Value where the baseload reference goes when a “Go to”
command is issued.
User Level: Operator
Enable (Remote Baseload)
Command
Visibility: Remote baseload in Use
This command will enable the remote baseload control mode.
User Level: Operator and baseload
Enabled
Disable (Remote Baseload)
Command
Visibility: Remote baseload in Use
This command will disable the remote baseload control mode.
User Level: Operator and baseload
enabled
Remote Reference
Monitor
Visibility: Remote baseload in Use
It shows the actual Remote Reference, from the analog input.
User Level: Monitor
Remote Baseload Fault
Monitor
Visibility: Remote baseload in Use
It shows if there is a signal fail on the analog input configured for
this function.
User Level: Monitor
Rate (Min to rated)
60.0 (1.0, 600.0) %/s
Visibility: Remote baseload in Use
The remote speed will follow the analog input configured for this
function, but will use this rate to prevent bumps on the reference.
Even if the analog input has big oscillations, the reference will
always ramp slowly.
User Level: Service
At the bottom of the screen there are two displays showing the actual load and the actual load reference.
Released
Summary of Contents for 505HT
Page 23: ...Manual 35116 505HT for Pelton Turbines Woodward 21 Figure 2 2 505D Outline Drawing Released...
Page 196: ...Manual 35116 505HT for Pelton Turbines Woodward 194 Figure F 10 Deflector Logic Released...
Page 197: ...Manual 35116 505HT for Pelton Turbines Woodward 195 Revision History New Manual Released...
Page 198: ...Manual 35116 505HT for Pelton Turbines Woodward 196 Declarations Released...