7
OPM-109
REV B
DR130F4
Generator
Wattage
123,000
130,000
130,000
130,000
Volts
120/240
120/208
120/240
277/480
Phase
Single
Three
Three
Three
PF
1.0
.80
.80
.80
Amps
512
451
391
195
&%6L]H
500
450
400
200
+HUW]
60
60
60
60
Engine
Model
FPT N67 TM1 6.7L
Starting System
12 Volt
0XIÀHU
Standard
)XHO&RQVXPSWLRQIXOOORDG
8.8 Gal/Hr
Generator Testing Resistance
Note: Review the Stamford Newage nameplate on your generator
before selecting the correct information below.
Model
Stamford
UCI274F
Winding Group
311
Resistances:
Rotor
1.19
Ohms
@22°C
Stator
0.0045 Ohms Per Ph @ 22°C
Exciter Rotor
0.136 Ohms Per Ph @ 22°C
Exciter Stator
18.0 Ohms @ 22°C
Voltage Regulator
SX460
Model
Stamford
UCI274F
Winding Group
06
Resistances:
Rotor
1.37
Ohms
@22°C
Stator
0.0037 Ohms Per Ph @ 22°C
Exciter Rotor
0.136 Ohms Per Ph @ 22°C
Exciter Stator
18.0 Ohms @ 22°C
Voltage Regulator
SX460
(QJLQH)OXLG6SHFL¿FDWLRQV
Fuel
ASTM D-975 -1D or 2D
EN590
or
equivalent
Oil
Type
SEE
LUBRICATION
SECTION
Oil Capacity
18 Quarts
Cooling System
50/50 mix
INTRODUCTION
PRODUCT DESCRIPTION
This engine-generator set is designed for unattended remote start
operation. It can be operated as part of a fully automatic standby power
system or independently as a local start unit in a prime power system.
The engine-generator set is fully tested at the factory prior to shipment
to insure proper operation of each individual component as well as the
total system’s performance and reliability.
The engine generator set consists of a multi-cylinder, liquid cooled
engine nominally operating at 1800 rpm. The generator frequency
UHJXODWLRQLVPDLQWDLQHGE\WKHHQJLQHJRYHUQRUW]
FSVIURPQRORDGWRUDWHGORDGIRUVWDQGDUGPHFKDQLFDOJRYHUQRUV
DQGW]RUEHWWHUIRUXQLWVHTXLSSHGZLWKDQHOHFWURQLF
JRYHUQRU7KHJHQHUDWRULVDVLQJOHEHDULQJGLUHFWGULYHURWDWLQJ¿HOG
GHVLJQ7KHJHQHUDWRULVFRQQHFWHGWRWKHHQJLQHÀ\ZKHHOYLDÀH[LEOH
drive disks. Generator set is skid mounted with isolation mounts
between the engine and base on all units.
A customer supplied 12 Volt battery is required to complete the
installation. Battery requirements are listed later under the battery
installation section.
Unit Orientation Note: All references used in this manual for unit
IDPLOLDUL]DWLRQDFFHVVDQGFRPSRQHQWORFDWLRQVRQWKH*HQHUDWRU6HW
DUHRULHQWHGIURPD723SODQ9,(:ZLWKHQJLQHDWWKH)5217DQG
generator to the REAR.
WINPOWER uses a common junction box for all customer control and
SRZHUFRQQHFWLRQVERWK$&RXWSXWDQG'&FRQWURO7KHFRPPRQ
electrical junction box is always on the left side at the generator end of
the machine.
The engine is controlled and Generator Set operation is monitored for
safe operation by a programmable microprocessor based electronic
(QJLQH&RQWURO0RGXOH(&0ZLWKDQ/&'GLJLWDOGLVSOD\7KH
generator set ECM control is mounted on a vertical pedestal on the
right side of the generator. The ECM is programmed with a cycle
cranking sequence - 3 cycles of 15 seconds on/15 seconds off, and
5 minute cool-down delay. The cool-down delay can be changed in
WKH¿HOGIURPWRPLQXWHVE\\RXULQVWDOOHU2WKHUIHDWXUHVWLPLQJ
cycles, set points, and signal output capabilities are possible. Consult
factory for procedure and passwords.
NOTICE:
These units will automatically transfer if a power outage occurs while
running in exercise mode.
GENERATOR SET
Every WINCO generator set has its own unique identity data plate.
7KLVGDWDSODWHLGHQWL¿HVWKHFRPSOHWHXQLWPRGHOQXPEHUWKHV\VWHP
serial number, and has links to the individual components that form the
generator set in our factory records. Several of the major components
also have their own individual data plates providing additional
information to document build data for warranty and replacement parts.