12
OPM-129/F
2. If the generator set is connected to an existing
distribution system, a fully isolated manual transfer switch
must be installed. The transfer switch prevents damage to
the generator and the other circuit components if main
line power is restored while the generator is connected.
Installing a transfer switch also permits the use of normal
fusing.
3. Many homes and construction sites are wired for at
least 60 to 100 Amp entrance service, much greater than
the capacity of this portable generator. When installing
the generator at these sites, a secondary emergency
distribution panel may have to be installed that works with
a GFCI breaker. The emergency distribution panel must be
installed by a licensed electrician according to all applicable
codes. The electrician will move the critical circuits to be
powered during the outage to the emergency panel. Keep
in mind only a limited amount of amperage is available from
the generator set. Some circuit breakers may still have to be
turned off to prevent an overload on the generator during
the initial start up. See the nameplate on your generator for
the amperage capabilities of your unit.
CAUTION: EQUIPMENT DAMAGE
Failure to properly limit and balance the load applied
to the generator will cause the generator to produce
low voltage and may damage the engine generator
set. It may also cause severe damage to the loads
connected to the generator at that time. Improper
loading of the generator set constitutes abuse and will
not be covered by warranty.