Installation and operating instructions Wilo-Stratos GIGA, GIGA-D, GIGA B
(11-22kW)
129
Table 13: Factory settings
14
Disposal
Proper disposal and appropriate recycling of this product prevents
damage to the environment and danger to your personal health.
Disposal in accordance with the regulations requires the product to be
drained and cleaned.
Oils and lubricants
Operating fluid must be collected in suitable tanks and disposed of in
accordance with the locally applicable guidelines.
Information on the collection of used
electrical and electronic products
NOTICE:
Disposal in domestic waste is forbidden!
In the European Union, this symbol can appear on the product, the
packaging or the accompanying documentation. It means that the
electrical and electronic products in question must not be disposed of
along with domestic waste.
To ensure proper handling, recycling and disposal of the used prod-
ucts in question, please note the following points:
• Only hand over these products at designated, certified collecting
points.
• Observe the locally applicable regulations!
Please consult your local municipality, the nearest waste disposal
site, or the dealer who sold the product to you for information on
proper disposal. Further recycling information can be found at
www.wilo-recycling.com.
Subject to change without prior notice!
4.3.1.0
Base-load pump
MA
5.1.1.0
Operating mode
Main/standby operation
5.1.3.2
Internal/external pump
cycling
Internal
5.1.3.3
Pump cycling time interval
24 h
5.1.4.0
Pump enabled/disabled
Approved
5.1.5.0
SSM
Collective fault signal
5.1.6.0
SBM
Collective run signal
5.1.7.0
Extern off
Collective Extern off
5.3.2.0
In1 (value range)
0–10 V active
5.4.1.0
In2 active/inactive
OFF
5.4.2.0
In2 (value range)
0-10 V
5.5.0.0
PID parameter
See chapter 9.4 "Setting the
control mode" on page 111
5.6.1.0
HV/AC
HV
5.6.2.0
Emergency operation
speed
Approx. 60 % of n
max
pump
5.6.3.0
Auto reset time
300 s
5.7.1.0
Display orientation
Display on original orientation
5.7.2.0
Pressure value correction
Active
5.7.6.0
SBM function
SBM: Run signal
5.8.1.1
Pump kick active/inactive
ON
5.8.1.2
Pump kick interval
24 h
5.8.1.3
Pump kick speed
n
min
Menu no. Designation
Factory-configured values
Summary of Contents for STRATOS GIGA