E025
Faulty contact
Electronic module has no
contact to motor
Request customer service
A
A
Winding interrupted Motor faulty
Request customer service
E026
WSK or PTC
interrupted
Motor faulty
Request customer service
B
A
Electronic
module error
E030
Excess temperature
Electronic module
Limited air supply to the
heat sink of the
electronic module
Provide unobstructed air
access
B
A
E031
Excess temperature,
hybrid/power
section
Ambient temperature too
high
Improve room ventilation
B
A
E032
Intermediate circuit
undervoltage
Voltage fluctuations in
the mains
Check electrical installation
F
D
E033
Intermediate circuit
overvoltage
Voltage fluctuations in
the mains
Check electrical installation
F
D
E035
DP/MP: multiple
instances of same
identity
Multiple instances of
same identity
Reallocate master and/or slave
(see chapter 9.2 "Double pump
installation/ Y-pipe
installation" on page 110)
E
E
Communica-
tion errors
E050
BMS communication
timeout
Bus communication
interrupted or timed out
Cable break
Check cable connection to
building automation
F
F
E051
Impermissible DP/
MP combination
Different pumps
Request customer service
F
F
E052
DP/MP
communications
timeout
Cable MP communication
defective
Check cable and cable
connections
E
E
Electronics
errors
E070
Internal
communication
error (SPI)
Internal electronics error
Request customer service
A
A
E071
EEPROM error
Internal electronics error
Request customer service
A
A
E072
Power section/
electronic module
Internal electronics error
Request customer service
A
A
E073
Impermissible
electronic module
number
Internal electronics error
Request customer service
A
A
E075
Charging relay
defective
Internal electronics error
Request customer service
A
A
E076
Internal transformer
defective
Internal electronics error
Request customer service
A
A
E077
24 V operating
voltage for
differential pressure
sensor defective
Differential pressure
sensor defective or
connected incorrectly
Check differential pressure
sensor connection
A
A
E078
Impermissible motor
number
Internal electronics error
Request customer service
A
A
E096
Infobyte not set
Internal electronics error
Request customer service
A
A
E097
Flexpump data
record missing
Internal electronics error
Request customer service
A
A
E098
Flexpump data
record invalid
Internal electronics error
Request customer service
A
A
E110
Motor
synchronisation
error
Internal electronics error
Request customer service
B
A
Classification
No.
Error
Cause
Remedy
Error type
HV