English
Installation and operating instructions Wilo-Stratos GIGA, GIGA-D, GIGA B
(11-22kW)
103
NOTICE:
A few elements are hidden under certain conditions and are therefore
skipped in the menu navigation.
If, for example, the external setpoint adjustment under menu
number <5.4.1.0> is set to “OFF”, the number <5.4.2.0> will be
hidden. Menu number <5.4.2.0> will only be visible if menu number
<5.4.1.0> has been set to “ON”.
No.
Designation
Type
Symbol Values/explanations
Display conditions
1.0.0.0
Setpoint
Setting/display of the setpoint
(for further information, see
chapter 8.6.1 "Adjusting the
setpoint" on page 99)
2.0.0.0
Control mode
Setting/display of the control
mode
(for further information, see
chapters 6.2 "Control modes" on
page 78 and 9.4 "Setting the
control mode" on page 111)
Constant speed control
Constant
Δ
p-c control
Variable
Δ
p-v control
PID-Control
2.3.2.0
Δ
p-v gradient
Setting the gradient of
Δ
p-v
(value in %)
Not displayed for all pump
types
3.0.0.0
Pump on/off
ON
Pump switched on
OFF
Pump switched off
4.0.0.0
Information
Information menus
4.1.0.0
Actual values
Display of current actual values
4.1.1.0
Actual values
sensor (In1)
Depending on current control
mode.
Δ
p-c,
Δ
p-v:
Value H in m
PID-Control: Value in %
Not displayed for constant
speed
4.1.3.0
Power
Current power input P
1
in W
4.2.0.0
Operating data
Display of operating data
The operating data refers to
the electronic module
currently being operated
4.2.1.0
Operating hours
Sum of the pump’s active hours
of operation
(counter can be reset by infrared
interface)
4.2.2.0
Consumption
Energy consumption in kWh/
MWh
4.2.3.0
Countdown, pump
cycling
Time to pump cycling in h
(at a resolution of 0.1 h)
Shown only for double pump
master and internal pump
cycling. Can be set in the
service menu <5.1.3.0>
±
±
±