Digital Input
Wieland Electric GmbH | BA000941 | 01/2014 (Rev. A)
29
At CPU, PROFIBUS and PROFINET the input respectively out area is embedded to the
corresponding address area.
IX =
Index for access via CANopen
SX = Subindex for access via EtherCAT
Addr.
Name
Bytes
Function
IX
SX
+0
Pll
1
State of the inputs
Bit 0: DI 0
Bit 1: DI 1
Bit 2: DI 2
Bit 3: DI 3
Bit 7 … 4: reserved
5000h
01h
02h
03h
04h
No byte of the output area is used by the module.
Type
Order number
ricos FLEX 4xDI DC 24 V
83.036.2200.0
Current consumption/power loss
Current consumption from backplane bus
55 mA
Power loss
0.6 W
Technical data digital inputs
Number of inputs
4
Cable length, shielded
1000 m
Cable length, unshielded
600 m
Rated load voltage
--
Current consumption from load voltage L+
(without load)
--
Rated value
DC 20.4 ... 28.8 V
Input voltage for signal "0"
DC 0 ... 5 V
Input voltage for signal "1"
DC 15 ... 28.8 V
Input voltage hysteresis
--
Frequency range
--
Input resistance
--
Input current for signal "1"
3 mA
Connection of Two-Wire-BEROs possible
Max. permissible BERO quiescent current
0.5 mA
Input delay of "0" to "1"
3 ms
Input delay of "1" to "0"
3 ms
Number of simultaneously utilizable inputs
horizontal configuration
4
Number of simultaneously utilizable inputs
vertical configuration
4
Input characteristic curve
IEC 61131-2, type 1
Initial data size
4 Bit
Status information, alarms, diagnostics
Status display
green LED per channel
Interrupts
no
Process alarm
no
Diagnostic interrupt
no
Diagnostic functions
no
Diagnostics information read-out
none
Module state
green LED
Module error display
red LED
Channel error display
none
Isolation
Between channels
--
Between channels of groups to
--
Between channels and backplane bus
Insulation tested with
DC 500 V
Input area
Output area
Technical data