Digital Input
26
Wieland Electric GmbH | BA000941 | 01/2014 (Rev. A)
2
6
3
7
4
8
1
5
1
2
3
4
5
6
7
8
2
6
3
7
4
8
1
5
DI
DC24V
0V
0
1
Position Function Type Description
1
DI 0
I
Digital input DI 0
2
DC 24 V
O
DC 24 V for sensor
3
0 V
O
GND
4
--
--
not connected
5
DI 1
I
Digital input DI 1
6
DC 24 V
O
DC 24 V for sensor
7
0 V
O
GND
8
--
--
not connected
I: Input, O: Output
At CPU, PROFIBUS and PROFINET the input respectively out area is embedded to the
corresponding address area. Information about accessing the system
ricos
FLEX may be
found in the manual of the CPU respectively of the corresponding bus coupler.
IX =
Index for access via CANopen
SX =
Subindex for access via EtherCAT
Addr.
Name
Bytes
Function
IX
SX
+0
Pll
1
State of the inputs
Bit 0: DI 0
Bit 1: DI 1
Bit 7 … 2: reserved
5000h
01h
02h
No byte of the output area is used by the module.
Type
Order number
ricos FLEX 2xDI DC 24 V
83.036.2100.0
Current consumption/power loss
Current consumption from backplane bus
55 mA
Power loss
0.5 W
Technical data digital inputs
Number of inputs
2
Cable length, shielded
1000 m
Cable length, unshielded
600 m
Rated load voltage
--
Current consumption from load voltage L+
(without load)
--
Rated value
DC 20.4 ... 28.8 V
Input voltage for signal "0"
DC 0 ... 5 V
Input voltage for signal "1"
DC 15 ... 28.8 V
Input voltage hysteresis
--
Frequency range
--
Input resistance
--
Input current for signal "1"
3 mA
In-/Output area
Input area
Output area
Technical Data