Basics and Assembly
Wieland Electric GmbH | BA000941 | 01/2014 (Rev. A)
23
Please regard at installation!
At potential differences between the grounding points, there may be a compensation
current via the isolation connected at both sides.
Remedy: Potential compensation line.
3.8
General data
Conformity and approval
Conformity
CE
2006/95/EG
Low-voltage directive
2004/108/EG
EMV directive
Approval
UL
UL 508
Approval for USA and Canada
Others
RoHS
--
Product is lead free
Protection of persons and device protection
Type of protection
--
IP20
Electrical isolation
To the field bus
--
Electrically isolated
To the process level
--
Electrically isolated
Insulation resistance
EN 61131-2
--
Insulation voltage to reference earth
Inputs/Outputs
--
AC / DC 50 V, test voltage AC 500 V
Protective measures
--
Against short circuit
Environment conditions to EN 61131-2
Climatic
Storage / transport
EN 60068-2-14
-25 °C …+70 °C
Operation
Horizontal
installation
EN 61131-2
0 °C …+60 °C
Vertical installation
EN 61131-2
0 °C …+60 °C
Air humidity
EN 60068-2-30
RH1 (without condensation, rel. humidity 10 %
… 95 %)
Pollution
EN 61131-2
Degree of pollution 2
Mechanical
Oscillation
EN 60068-2-6
1 g, 9 Hz ... 150 Hz
Shock
EN 60068-2-27
15 g, 11 ms
Mounting conditions
Mounting place
--
In the control cabinet
Mounting position
--
Horizontal und vertical
NOTE