Digital Output
Wieland Electric GmbH | BA000941 | 01/2014 (Rev. A)
35
2
6
3
7
4
8
1
5
1
2
3
4
5
6
7
8
2
6
3
7
4
8
1
5
DO
DC24V
0V
0
1
Position Function Type Description
1
DO 0
O
Digital output DO 0
2
DC 24 V
O
DC 24 V
3
0 V
O
GND for actuator
4
--
--
not connected
5
DO 1
O
Digital output DO 1
6
DC 24 V
O
DC 24 V
7
0 V
O
GND for actuator
8
--
--
not connected
O: Output
At CPU, PROFIBUS and PROFINET the input respectively out area is embedded to the
corresponding address area.
IX =
Index for acces via CANopen
SX = Subindex for acces via EtherCAT
No byte of the input area is used by the module.
Addr.
Name
Bytes
Function
IX
SX
+0
PlQ
1
State of the outputs
Bit 0: DO 0
Bit 1: DO 1
Bit 7 … 2: reserved
5200h
01h
02h
Type
Order number
ricos FLEX 2xDO DC 24 V 0,5 A
83.036.3100.0
Current consumption/power loss
Current consumption from backplane bus
55 mA
Power loss
0.4 W
Technical data digital outputs
Number of outputs
2
Cable length, shielded
1000 m
Cable length, unshielded
600 m
Rated load voltage
DC 20.4 ... 28.8 V
Current consumption from load voltage L+
(without load)
5 mA
Total current per group, horizontal
configuration, 40°C
1 A
Total current per group, horizontal
configuration, 60°C
1 A
Total current per group, vertical
configuration
1 A
Output current at signal "1", rated value
0.5 A
Output delay of "0" to "1"
30 µs
In-/Output area
Input area
Output area
Technical data