Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014
Page 157
Loop 1 Gain Set 4 Breakpoint
Gain Scheduling PID Set 3 To 4 Switch Point
Dec
4371
20755 41510
RW
Value (SP or PV) gain scheduling switches from PID Set 3 To 4.
Value between Set 3 Breakpoint & Scaled Input 1 Upper Limit.
Hex
1113
5113
A226
Loop 1 Gain Set 5 Breakpoint
Gain Scheduling PID Set 4 To 5 Switch Point
Dec
4372
20756 41512
RW
Value (SP or PV) gain scheduling switches from PID Set 4 To 5.
Value between Set 4 Breakpoint & Scaled Input 1 Upper Limit.
Hex
1114
5114
A228
Loop 1 Cascade Mode
Value
Cascade Master/Slave Link Status
Dec
4393
20777 41554
RW
0
Cascade Closed
Hex
1129
5129
A252
1
Cascade Open
Loop 1 Ratio NO Constant
Ratio NO Constant For Atomizing Air
Dec
4387
20771 41542
RW
0 to 9999 atomizing air value,
Added to the x1 value in ratio mode (air flow is x1 + NO).
Hex
1123
5123
A246
Loop 1 Ratio Sfac Constant
Ratio Sfac Constant
Dec
4388
20772 41544
RW
Ratio control mode scaling factor. Adjustable from 0.010 to
99.999
Hex
1124
5124
A248
Loop 2 Control Parameters
Parameter Name & Register Address
Integer Int +1
Float
Access
Values
& Descriptions
Loop 2 Manual Control Select
Value
Selection
Dec
4408
20792 41584
RW
0
Automatic Mode
Hex
1138
5138
A270
1
Manual Mode
Loop 2 Control Enable Select
Value
Control Enable Selection
Dec
4409
20793 41586
RW
0
Disabled
Hex
1139
5139
A272
1
Enabled
Loop 2 Auto/Manual Access
Value
Operator Access To Auto/Manual Control
Dec
4494
20878 41756
RW
0
Off
Hex
118E
518E
A31C
1
On
Loop 2 Control Enable Access
Value
Operator Access To Control Enable/Disable
Dec
4495
20879 41758
RW
0
Off
Hex
118F
518F
A31E
1
On
Loop 2 Primary Cycle Time
Cycle Time For Primary Control Outputs
Dec
4303
20687 41374
RW
0.5 to 512.0 Seconds
Hex
10CF
50CF
A19E
Loop 2 Secondary Cycle Time
Cycle Time For Secondary Control Outputs
Dec
4304
20688 41376
RW
0.5 to 512.0 Seconds
Hex
10D0
50D0
A1A0
Loop 2 Control Selection
Value
Control Actuator Type Selection
Dec
4407
20791 41582
RW
0
Standard
(Time Proportioned or Continuous PID)
Hex
1137
5137
A26E
1
VMD
(3-Point Stepping for Valve Motor Drive)
Loop 2 Control type
Value
Primary Only or Primary & Secondary
Dec
4410
20794 41588
RW
0
Single
(Primary Only Control)
Hex
113A
513A
A274
1
Dual Control
(Primary & Secondary Control)