Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014
Page 165
Alarm 2 Status
Value
Alarm 2 Status
Dec
6164
22548 45096
RO
0
Inactive
Hex
1814
5814
B028
1
Active
Alarm 2 Inhibit Status
Value
Alarm 2 Inhibit Status
Dec
6165
22549 45098
RO
0
Not Inhibited
Hex
1815
5815
B02A
1
Inhibited
Alarm 2 Label
Main Language Name for Alarm 2 In Status Screen
Dec
6167
22551 45102
RW
8 ASCII characters replacing the title "Alarm 2" in alarm status
screens when main display language is used, read/written with
Modbus functions 16 or 23. Valid characters are
0 to 9, a to z, A
to Z, plus ß ö ( ) - and _
.
Hex
1817
5817
B02E
Alarm 2 Alternate Label
Alternate Language Name for Alarm 2 In Status Screen
Dec
6168
22552 45104
RW
8 ASCII characters replacing the title "Alarm 2" in alarm status
screens when the alternate language is used, read/written with
Modbus functions 16 or 23. Valid characters are
0 to 9, a to z, A
to Z, plus ß ö ( ) - and _
.
Hex
1818
5818
B030
Alarm 2 Minimum Duration
Alarm 2 Minimum Duration
Dec
6169
22553 45106
RW
Minimum time alarm 2 must be passed its threshold before
activating (deactivation is not affected by this parameter).
From 0 to 9999 secs
Hex
1819
5819
B032
Alarm 3 Input Source
Value
Source
Dec
6175
22559 45118
RW
0
Input 1
Hex
181F
581F
B03E
1
Input 2
2
Aux A Input
3
Control Loop 1 Primary Power
4
Control Loop 1 Secondary Power
5
Control Loop 2 Primary Power
6
Control Loop 2 Secondary Power
7
Loop 1
8
Loop 2
Alarm 3 Type
Value
Alarm 3 Type
Dec
6176
22560 45120
RW
0
Unused
Hex
1820
5820
B040
1
Process High Alarm
2
Process Low Alarm
3
Deviation Alarm (SP-PV)
4
Band Alarm
5
Input Rate of Change
6
Input/Sensor Break Alarm
7
Loop Alarm
10
% memory used
11
High Power Alarm
12
Low Power Alarm