Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014
Page 174
Record Cascade Slave Primary Power
Value
Record Primary Power Value of Cascade Slave
Dec
7533
23917 47834
RW
0
Do Not Record Primary Power
Hex
1D6D
5D6D
BADA
1
Record Primary Power Of Slave
Record Slave Secondary Power
Value
Record Slave Secondary Power in Cascade Mode
Dec
7538
23922 47844
RW
0
Do Not Record Secondary Power
Hex
1D72
5D72
BAE4
1
Record Secondary Power Of Slave
Record Ratio PV Input 1
Value
Record Ratio Mode Input 1 Process Value
Dec
7534
23918 47836
RW
0
Do Not Record PV
Hex
1D6E
5D6E
BADC
1
Record Ratio Input 1 PV Value
Record Ratio PV Input 2
Value
Record Ratio Mode Input 2 Process Value
Dec
7535
23919 47838
RW
0
Do Not Record PV
Hex
1D6F
5D6F
BADE
1
Record Ration Input 2 PV Value
Record Ratio SP
Value
Record Ratio Mode Setpoint
Dec
7536
23920 47840
RW
0
Do Not Record SP
Hex
1D70
5D70
BAE0
1
Record Ratio Mode SP Value
Record Ratio Power
Value
Record Ratio Mode Power Output Value
Dec
7537
23921 47842
RW
0
Do Not Record Ratio Power
Hex
1D71
5D71
BAE2
1
Record Ratio Mode Power
Trigger Recording On Alarm 1
Value
Alarm 1 To Trigger Recording
Dec
7584
23968 47936
RW
0
Off
Hex
1DA0
5DA0
BB40
1
Trigger On Alarm 1 (if auto-trigger = profile or alarm)
Trigger Recording On Alarm 2
Value
Alarm 2 To Trigger Recording
Dec
7685
24069 48138
RW
0
Off
Hex
1E05
5E05
BC0A
1
Trigger On Alarm 2 (if auto-trigger = profile or alarm)
Trigger Recording On Alarm 3
Value
Alarm 3 To Trigger Recording
Dec
7686
24070 48140
RW
0
Off
Hex
1E06
5E06
BC0C
1
Trigger On Alarm 3 (if auto-trigger = profile or alarm)
Trigger Recording On Alarm 4
Value
Alarm 4 To Trigger Recording
Dec
7687
24071 48142
RW
0
Off
Hex
1E07
5E07
BC0E
1
Trigger On Alarm 4 (if auto-trigger = profile or alarm)
Trigger Recording On Alarm 5
Value
Alarm 5 To Trigger Recording
Dec
7688
24072 48144
RW
0
Off
Hex
1E08
5E08
BC10
1
Trigger On Alarm 5 (if auto-trigger = profile or alarm)
Trigger Recording On Alarm 6
Value
Alarm 6 To Trigger Recording
Dec
7613
23997 47994
RW
0
Off
Hex
1DBD
5DBD
BB7A
1
Trigger On Alarm 6 (if auto-trigger = profile or alarm)
Trigger Recording On Alarm 7
Value
Alarm 7 To Trigger Recording
Dec
7614
23998 47996
RW
0
Off
Hex
1DBE
5DBE
BB7C
1
Trigger On Alarm 7 (if auto-trigger = profile or alarm)
Sample Size
Data Recording Sample Size
Dec
7595
23979 47958
RO
The size (in bytes) for recording sample with current settings
Hex
1DAB
5DAB
BB56
Summary of Contents for Pro-EC44