“For Service” Contact Details - Lines 1 to 7
Dec
400
16784 33568
RW
7 lines of user definable text - 25 ASCII characters per line which
can be read or written using Modbus functions 16 or 23.
Note:
The number of ASCII characters transmitted per line
must be EVEN. If the text string you wish to send has an
odd number, place an additional space character at the end.
The space character is 20 hex.
Valid characters are 0 to 9, a to z, A to Z, plus ß ö ( ) - and _.
Example. To write
“My Company Name”
to line 1 send:
[ADDRESS], 16, 01, 90, 00, 08, 10,
4D, 79, 20, 43, 6F, 6D, 70,
61, 6E, 79, 20, 4E, 61, 6D, 65,
20
,
[CRC]
Hex
0190
4190
8320
Contact Details 2
Dec
401
16785 33570
RW
Hex
0191
4191
8322
Contact Details 3
Dec
402
16786 33572
RW
Hex
0192
4192
8324
Contact Details 4
Dec
403
16787 33574
RW
Hex
0193
4193
8326
Contact Details 5
Dec
404
16788 33576
RW
Hex
0194
4194
8328
Contact Details 6
Dec
405
16789 33578
RW
Hex
0195
4195
832A
Contact Details 7
Dec
406
16790 33580
RW
Hex
0196
4196
832C
Profiler Control & Status Parameters
Parameter Name & Register Address
Integer Int +1
Float
Access
Values
& Descriptions
Active Profiler
Active Profiler Number
Dec
8243
24627 49254
RW
Currently selected profile number (0 to 63)
Hex
2033
6033
C066
Active Segment
Active Segment Number
Dec
8244
24628 49256
RO
The active segment number (1 to 255) of the selected profile.
Hex
2034
6034
C068
Profiler Control Commands
Value
Profiler Command
Dec
8245
24629 49258
RW
0
Do nothing
Hex
2035
6035
C06A
1
Run the currently selected profile
Note:
The Profiler Control Commands
must be followed by a Profiler Control
Confirmation Action command,
otherwise the command will not be
implemented.
2
Hold the currently running profile
3
Abort the currently running profile
4
Jump to the next segment
5
Release the hold
6
Exit profiler, return to controller mode
8
Select a profile to be run but not start it
Profiler Control Confirmation Action
Value
Implement Profiler Command
Dec
8257
24641 49282
RW
0
Do not Implement Command
Hex
2041
6041
C082
1
Implement previous Profiler Command
Enable Edit While Running
Value
Operator Editing of Current Running Profile
Dec
8262
24646 49292
RW
0
Editing of running profile forbidden
Hex
2046
6046
C08C
1
Editing of running profile via Keypad allowed