Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014
Page 154
Loop 1 Combined Power
Loop 1 Combined Primary & Secondary Power Level
Dec
4331
20715 41430
RO
The current loop 1 combined PID power level (-100 to 100%)
Hex
10EB
50EB
A1D6
Loop 1 Pre-Tune Status
Value
Pre-Tune Status For Loop 1
Dec
4332
20716 41432
RO
0
Inactive
Hex
10EC
50EC
A1D8
1
Active
Loop 1 Self-Tune Status
Value
Self-Tune Status For Loop 1
Dec
4333
20717 41434
RO
0
Inactive
Hex
10ED
50ED
A1DA
1
Active
Loop 1 Loop Alarm status
Value
Loop Alarm Status For Loop 1
Dec
4334
20718 41436
RO
0
Inactive
Hex
10EE
50EE
A1DC
1
Active
Loop 1 Input Failure Pre-set Power
Loop 1 Input Sensor Break Pre-set Power
Dec
4335
20719 41438
RW
The pre-defined power output applied if input signal is lost
0 to 100% (-100% to 100% for dual control).
Hex
10EF
50EF
A1DE
Loop 1 Auto Pre-tune
Value
Auto Pre-Tune At Every Power-up For Loop 1
Dec
4336
20720 41440
RW
0
Disabled
Hex
10F0
50F0
A1E0
1
Enabled
Pre-tune Secondary Status
Value
Pre-tune Secondary Status
Dec
4341
20725 41450
RO
0
No Additional Information
Hex
10F5
50F5
A1EA
1
PV within 5%
(Pre-Tune cannot run)
2
Manual Control Enabled
(Pre-Tune cannot run)
3
Control has On/Off element
(Pre-Tune cannot run)
4
Input not valid
(Pre-Tune cannot run)
5
Control Disabled
(Pre-Tune cannot run)
6
Profile Running
(Pre-Tune cannot run)
7
Setpoint Ramping
(Pre-Tune cannot run)
Self-tune Secondary Status
Value
Self-tune Secondary Status
Dec
4342
20726 41452
RO
0
No Additional Information
Hex
10F6
50F6
A1EC
2
Manual Control Enabled
(Self-Tune cannot run)
3
Control has On/Off element
(Self-Tune cannot run)
4
Input not valid
(Self-Tune cannot run)
5
Control Disabled
(Self-Tune cannot run)
Loop 1 Anti Wind-up Limit
Loop 1 Anti Wind-up Limit
Dec
4391
20775 41550
RW
Power level where integral action is suspended.
Adjustable from 10.0 to 100.0% of PID power.
Hex
1127
5127
A24E
Loop 1 Motor Travel Time
Loop 1 Motor Travel Time
Dec
4343
20727 41454
RW
The motor travel time (from fully open to fully closed) for 3-point
stepping VMD control. Adjustable from 5 to 300 seconds.
Hex
10F7
50F7
A1EE
Loop 1 Minimum Motor On Time
Loop 1 Minimum Motor On Time
Dec
4344
20728 41456
RW
Minimum drive effort to begin moving valve for 3-point stepping
VMD control. In seconds, from 0.02 to 1/10 of Motor Travel Time
Hex
10F8
50F8
A1F0
Loop 1 VMD Break Action
Value
Loop 1 Sensor Break Action For VMD Control
Dec
4401
20785 41570
RW
0
Close Valve Output On
Hex
1131
5131
A262
1
Open Valve Output On
Loop 1 Valve Close Limit
Loop 1 Minimum Valve Position
Dec
4376
20760 41520
RW
Minimum position to drive valve in VMD Mode
from the valve close limit+1% to 100.0%
Hex
1118
5118
A230
Summary of Contents for Pro-EC44
Page 1: ...Pro EC44 2 Loop Graphical Profile Controller Recorder Pro EC44 User Guide 59540 2 ...
Page 2: ......
Page 6: ......