Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014
Page 114
Calibration Reminder Parameters
Parameter Name & Register Address
Integer Int +1
Float
Access
Values
& Descriptions
Calibration Reminder Enable
Value
Calibration Reminder Status
Dec
1048
17432 34864
RW
0
Disabled
Hex
0418
4418
8830
1
Enabled
Calibration Reminder Date
Value
Calibration Status
Dec
n/a
n/a
34866
RW
This can be entered only as a floating point number. When
converted to binary the least significant 19 bits represents the
date in this format:
Hex
n/a
n/a
8832
www
DDDDD
MMMM
YYYYYYY
YYYYYYY = YEAR
MMMM = MONTH
DDDDD = DAY OF MONTH
(1-31 but must be valid)
www
=
Day of the week
The day of week portion
is calculated from the date (
Read Only
).
Example with date set to
31/07/2012
Day (31) = 11111
Month (7) = 0111
Year (12) = 0001100
Bits 17 and higher are ignored when writing so
11111 0111
0001100
(64396 decimal) is just one of many possible numbers
to write as 31/07/2012, and when reading the date back, the
number returned is
10
11111 0111 0001100
(195468 decimal) because bits 17-19
are
010
(to represent “Tuesday”).
Universal Process Input 1 Parameters
Parameter Name & Register Address
Integer Int +1
Float
Access
Values
& Descriptions
Universal Process Input 1 Type
Value
Process Input Type
Dec
1024
17408 34816
RW
0
B Type Thermocouple
Hex
0400
4400
8800
2
C Type Thermocouple
4
D Type Thermocouple
6
E Type Thermocouple
8
J Type Thermocouple
10
K Type Thermocouple
12
L Type Thermocouple
14
N Type Thermocouple
16
R Type Thermocouple
18
S Type Thermocouple
20
T Type Thermocouple
22
PtRh 20%: 40% Thermocouple
24
PT100 RTD
26
NI120 RTD
28
0 to 20mA DC
29
4 to 20mA DC
30
0 to 50mV DC