39
Safety Light Array
From
Function
To
Relay Unit Connections
Terminal 1
NO 13
Machine contact
Terminal 2
NO 23
Machine contact
Terminal 3
NO 24
Machine contact
Terminal 4
NO 14
Machine contact
Terminal 5
NO 43
Machine contact
Terminal 6
NO 33
Machine contact
Terminal 7
NO 34
Machine contact
Terminal 8
NO 44
Machine contact
Terminal 9
OSSD 1
Pin 3 socket 1 (receiver)
Terminal 10
OSSD 2
Pin 6 socket 1 (receiver)
Terminal 11
unused
Terminal 12
0 V
Pin 7 socket 1 (receiver)
Terminal 13
unused
Terminal 14
Contactor monitor
Pin 5 socket 1 (receiver)
Terminal 15
24 V
Pin 2 socket 1 (receiver)
Terminal 16
unused
DIP Switch Settings: Receiver
Serial Communication
Cascading
Timing
Restart Inhibit
8
7
6
5
4
3
2
1
ON OFF
Contactor Monitoring
Reduced Resolution
Fix Blanking
S1
6.2 Muting Module
The PMUT-X1P add-on module allows for muting mode operation with the Light Array. Certain objects can be
passed through the safety field without switching the safety output in muting mode. For example, material can be
fed through the safety field, although reach-in or step-in is nevertheless detected. The muting module allows dif-
ferent types of muting and cyclic operation modes. The use is described in the operating instruction of the muting
module.