Connection and Installation to the Machine
From
To
Transmitter Wiring
Pin 1
24 V DC
24 V DC supply voltage
Pin 2
Unused
Pin 3
0 V
0 V supply voltage
Pin 4
Earth/shield
Operational earth
Receiver Wiring
Pin 1
Signal output
Free
Pin 2
24 V DC
24 V DC supply voltage
Pin 3
OSSD1 output
PLC or relay
Pin 4
Acknowledge
Free
Pin 5
Contactor monitor
Free
Pin 6
OSSD2 output
PLC or relay
Pin 7
0 V
0 V supply voltage
Pin 8
Earth/shield
Operational earth
DIP Switch Settings: Receiver
Serial Communication
Cascading
Timing
Restart Inhibit
8
7
6
5
4
3
2
1
ON OFF
Contactor Monitoring
Reduced Resolution
Fix Blanking
S1
4.3 Default Settings
The Safety Light Array offers various types of functions without any additional devices. The following table
provides an overview of possible functions, as well as the product’s respective default settings.
Characteristic/Function Type
Default Settings
DIP-Switch
Position: OFF
Safety Operating Mode
Active
Start-Up inhibit and Restart Inhibit
Not active
Contactor Monitoring
Not active
Fix Blanking
Not active
Reduced Resolution
Not active
Cascading
Not active